From 9.2
it
is known that the.torque vs speed characteristic of a turbine decreases always
,,g
the speed.
In
contrast, the slope of the generator torque characteristic depends on the grid load,
whereas the turbine characteristic can
be
changed (by means of the gate position). The
perator characteristic results from the accidental grid load. This causes the main
disturbance to the control loop considered.
~ssuming the intersection point of both the characteristics to be stable and neglectin?
inertia effects, the momentary speed of a set would result from the accidental position of
the intersection point of both characteristics. Now the essential task of the speed governor
of
a leading plant is to have a settled speed .at the intersection point that is assigned to
the load according to the proportional band (permanent speed droop) of the set,
i.e.,
adapting the gate position to the randomly varying grid load.
Fig. 11.2.3 shows typical curves of grid-load-induced generator torque vs speed. Curve a)
is due to machine tools, curve
b)
is due to pumps and blowers, curve c) is due
to
resistor
load (bulbs, electrolytic cells etc.). This figure reveals also the so-called automatic regula-
tion or self control of the grid by a change of load,
M,
to
M,
or
M,,
that results ultimately
in a new stable operation point
C
or
B.
This is characterized by a slope
of
the load torque
vs
speed that drops steeper than that of the turbine torque vs speed [11.23].
Contrary to this automatic regulation of a load due to machine tools or pumps and
blowers, a load due to resistors usually has no self control (automatic control). At any rate
the set requires the assistance of a speed governor for not obtaining indefinitely increasing
or decreasing speed in case of disturbances.
11.2.1.4.
The tasks
of
speed
control
I.
Frequency control: This holds especially when the alternator supplies a grid by itself
and has a set proportional band
6,
=
(n,,,
-
nmi,,)/n, (permanent speed droop). In this
n,,,
n,,, n, are the maximum, minimum and mean speed, or grid frequency in thz
working scope of the set. By the proportionzl band
a
speed is assigned to a certain load
so as to have full load at minimum speed
n,,, and zero load at maximum speed n,,.
According to Fig. 11.2.4a, in consequence of a certain proportional band
6,
of the
individual sets, a certain frequency change An effects different changes
A
P,,
A
P,
to the
output of these sets 1 and
2.
Together with the speed adjustment (111) a non-vanishing
proportional band enables also synchronization of an isolated set.
By
virtue of the then
existing slope of the set's load vs
speed characteristic it is possible to effect a translation
of
the
latter by actuating the speed adjustment device such as to shift the point of zero
load from zero
speed with the set at rest to synchronous speed needed for synchroniza-
tion,
(1 1.21, Fig. 1 1.2.4 b.
In a large AC grid the frequency varies only within a rather small band of up to
1
or
2
%.
For base load plants
6,
is rather large, namely 0,04.. .0,05. This guarantees a rather
constant output when the frequency varies within a certain band.
Contrary to this in a peak load plant
6,
=
0,01
.
.
.0,02. This facilitates a rather sensibile
variation of output in the case of a modest frequency change. In other words this low
6,
enables the control of frequency especially by a powerful peak load plant 3. The frequency
load coordination by the proportional band is also important for a certain load distribu-
tion in the plants of a certain grid (Fig.
11.2.4~).
A
certain
5,
may be effected mechanically or electromechanically. The first
by
a cam
which, in the steady state position of the sleeve valve, assigns a certain servomotor