
38 Power Quality 1065
Unlike limits set forth in various IEC Standards, IEEE 519-
1992 established the “point of common coupling,” or PCC as
the point at which harmonic limits shall be evaluated. In most
cases (recall that IEEE 519-1992 is a “recommended practice”),
this point will be:
1. In the supply system owned by the utility company,
2. The closest electrical point to the end-user’s premises,
and
3. As in (2), but further restricted to points where other
customers are (or could be in the future) provided with
electric service.
In this context, IEEE 519-1992 harmonic limits are designed
for an entire facility and should not be applied to individual
pieces of equipment without great care.
Because the PCC is used to evaluate harmonic limit com-
pliance, the system strength (impedance) is measured at this
point and is described in terms of available (three-phase)
short-circuit current. Also, the end-user’s maximum average
demand current is evaluated at this point. Maximum demand
is evaluated based on one of the following:
1. The maximum value of the 15 or 30 minute average
demand, usually considering the previous 12 month’s
billing history or
2. The connected kVA or horsepower, perhaps multiplied
by a diversity factor.
The ratio of I
SC
to I
L
, where I
SC
is the available fault cur-
rent and I
L
is the maximum demand current, implements the
founding concept of IEEE 519-1992: larger end-users can cre-
ate more harmonic currents, but the specific level of current
that any end-user may produce is dependent on the strength
of the system at the PCC. Tables 38.3–38.5 show the harmonic
current limits in IEEE 519-1992 for various voltage levels.
In general, it is the responsibility of the end-user to insure
that their net harmonic currents at the PCC do not exceed the
values given in the appropriate table. In some cases, usually
TABLE 38.3 Current distortion limits for general distribution systems,
120 V–69 kV
Maximum harmonic current distortion in percent of I
L
I
SC
/I
L
<11 11 ≤ h < 17 17 ≤ h < 23 23 ≤ h < 35 h ≥ 35 TDD
<20
1
4.0 2.0 1.5 0.6 0.3 5.0
20<50 7.0 3.5 2.5 1.0 0.5 8.0
50<100 10.0 4.5 4.0 1.5 0.7 12.0
100<1000 12.0 5.5 5.0 2.0 1.0 15.0
≥1000 15.0 7.0 6.0 2.5 1.4 20.0
Individual harmonic order h (odd harmonics).
Even harmonics are limited to 25% of the odd harmonic limits above.
Current distortions that result in a dc offset are not allowed.
1
All power generation equipment is limited to these values of current
distortion regardless of the value of I
SC
/I
L
.
TABLE 38.4 Current distortion limits for general subtransmission
systems, 69.001–161 kV
Maximum harmonic current distortion in percent of I
L
I
SC
/I
L
<11 11 ≤ h < 17 17 ≤ h < 23 23 ≤ h < 35 h ≥ 35 TDD
<20
1
2.0 1.0 0.75 0.3 0.15 2.5
20<50 3.5 1.75 1.25 0.5 0.25 4.0
50<100 5.0 2.25 2.0 0.75 0.35 6.0
100<1000 6.0 2.75 2.5 1.0 0.5 7.5
≥1000 7.5 3.5 3.0 1.25 0.7 10.0
Individual harmonic order h (odd harmonics).
Even harmonics are limited to 25% of the odd harmonic limits above.
Current distortions that result in a dc offset are not allowed.
1
All power generation equipment is limited to these values of current
distortion regardless of the value of I
SC
/I
L
.
TABLE 38.5 Current distortion limits for general transmission systems,
>161 kV
Maximum harmonic current distortion in percent of I
L
I
SC
/I
L
<11 11 ≤ h < 17 17 ≤ h < 23 23 ≤ h < 35 h ≥ 35 TDD
<50
1
2.0 1.0 0.75 0.3 0.15 2.5
≥50 3.0 1.5 1.15 0.45 0.22 3.75
Individual harmonic order h (odd harmonics).
Even harmonics are limited to 25% of the odd harmonic limits above.
Current distortions that result in a dc offset are not allowed.
1
All power generation equipment is limited to these values of current
distortion regardless of the value of I
SC
/I
L
.
TABLE 38.6 Voltage distortion limits
Bus voltage at PCC Individual harmonic Total voltage
magnitude (%) distortion (THD in %)
≤69 kV 3.0 5.0
69.001–161 kV 1.5 2.5
>161 kV 1.0 1.5
associated with parallel resonance involving a utility-owned
capacitor bank, it is possible that all customers will be within
the prescribed limits, but voltage distortion problems exist.
In these cases, it is generally the responsibility of the supply
utility to insure that excessive voltage distortion levels are not
present. The harmonic voltage limits that are recommended
for utility companies are given in Table 38.6.
38.5 Conclusions
In this chapter, various power quality phenomena have been
described, with particular focus on the implications on power