
190  Chapter 9  Program Control Instructions
example, if maintenance personnel are performing rou-
tine maintenance on a de-energized motor, the machine 
may suddenly become energized by someone forcing the 
motor to turn on. This is why a hardwired master control 
circuit is required for the I/O rack. The hardwired circuit 
will provide a method of physically removing power to 
the I/O system, thereby ensuring that it is impossible to 
energize any inputs or outputs when the master control 
is off.   
  9.6  Safety Circuitry 
  Suf cient emergency circuits must be provided to stop ei-
ther partially or totally the operation of the controller or 
the controlled machine or process. These circuits should 
be hardwired outside the controller so that in the event of 
total controller failure, independent and rapid shutdown 
is available. 
  Figure9-23  shows typical safety wiring requirements 
for a PLC installation. The safety requirements of this in-
stallation can be summarized as follows: 
•        A main disconnect switch is installed on the 
incoming power lines as a means of removing 
power from the entire programmable controller 
system.  
•        The main power disconnect switch should be lo-
cated where operators and maintenance personnel 
have quick and easy access to it. Ideally, the discon-
nect switch is mounted on the outside of the PLC 
enclosure so that it can be accessed without opening 
the enclosure.  
•        In  addition  to  disconnecting  electrical  power,  you 
should de-energize, lock out, and tag all other 
sources of power (pneumatic and hydraulic) before 
you work on a machine or process controlled by the 
controller.  
•        An isolation transformer is used to isolate the con-
troller from the main power distribution system and 
step the voltage down to 120 VAC.  
•        A hardwired master control relay is included to pro-
vide a convenient means for emergency controller 
shutdown. Because the master control relay allows 
the placement of several emergency-stop switches 
in different locations, its installation is important 
from a safety standpoint.  
•        Overtravel  limit  switches  or  mushroom  head  emer-
gency stop pushbuttons are wired in series so that 
when one of them opens, the master control is 
de-energized.  
•        This removes power to input and output device 
circuits. Power continues to be supplied to the 
2.      With the right mouse button, click the I/O bit you 
want to force.  
3.      From the menu that appears, select Go to Data Table 
or select Force On or Force Off.  
4.      From the associated data table that appears, click on 
the Forces button.  
5.      The Forces version of the data table appears with 
the selected bit highlighted. Click on this bit with 
the right mouse button.  
6.      From the menu that appears, you can force the se-
lected bit on or off.     
 Exercise care when you use forcing functions.  If 
used incorrectly, force functions can cause injuries 
to persons working around a system, and/or equip-
ment damage.  For this reason, forcing functions should 
be used only by personnel who completely understand 
the circuit and the process machinery or driven equip-
ment ( Figure9-22 ). You must understand the potential 
effect that forcing given inputs or outputs will have on 
machine operation in order to avoid possible personal 
injury and equipment damage. Before using a force 
function, check whether the force acts on the I/O point 
only or whether it acts on the user logic as well as on the 
I/O point. Most programming terminals and PLC CPUs 
provide some visible means of alerting the user that a 
force is in effect.  
 In situations in which rotating equipment is involved, 
the force instruction can be extremely dangerous. For 
  Figure 9-22   Exercise care when you use forcing functions.   
 
 Source: Courtesy Givens Engineering Inc. 
pet10882_ch09_176-199.indd   190pet10882_ch09_176-199.indd   190 7/23/10   10:05 PM7/23/10   10:05 PM