VOLTAGE STABILITY
10-6
Note that at unity power factor,
φ
= 0. Therefore
X
V
P
S
2
2
max
= (10.14)
and
S
S
R
V
V
V 7.0
2
≈= (18.15)
Using the expression for power,
δ
sin
X
VV
P
RS
= , and equations (10.14) and (10.15),
δ
at
maximum or critical power is given by
δ
= 45°. In the absence of specific voltage support at the
receiving end, the maximum power that can be delivered at unity power factor is, therefore,
given by equation (10.14), and this occurs at
δ
= 45°.
At power factors other than unity, from equations (10.12) and (10.13), and using the usual
expression for power transfer,
δ
φ
φ
δ
φ
φ
sin
cos
sin1
2
sin
cos
sin1
2
2
22
−
==
−
X
V
X
VV
X
V
SSRS
from which
2
sin1
sin
φ
δ
−
=
(10.16)
Therefore, at lagging power factors, the maximum power occurs at a power angle less than 45
°.
This point has important bearings in actual power system operation.
Problem: Show that when the transmission line has appreciable resistance, the maximum power
transfer at unity pf in the absence of specific voltage support at the receiving end occurs at a
power angle
δ
=
α
/2, where
α
is given by )/(tan
1
RX
−
=
α
, where R is the line resistance.
Plots of receiving-end voltage against power delivered at various power factors for a typical
system are shown in Figure 10.4. For satisfactory performance with good voltage profile the
operation should normally be restricted on the upper portion of the curves, well away from the
loading limit. It can be seen that when the system is operating close to the loading limit at a
given power factor, a slight change in the power factor can initiate a run away situation if the
load tended to restore to the demanded level. It can also be seen that although at unity and
lagging power factors the receiving-end voltage continuously drops as the power delivered is
increased and the voltage at maximum power is quite low compared with the sending-end
voltage, the situation is different at leading power factors. At leading power factors, the
receiving-end voltage can actually rise with increase in the power delivered, and the voltage at
maximum power can be quite high. In other words, at leading power factors, or if sufficient
reactive support is provided at the receiving end, the voltage at the maximum power point can be
comparable to or even higher than the sending-end voltage, although the maximum power would
be quite high. Therefore, the magnitude of the receiving-end voltage alone is not a good indicator
of closeness to the critical or maximum power point. In the same way, the change in the
receiving-end voltage corresponding to a change in the power delivered, dV
R
/dP, cannot be used
as a reliable guide to predict closeness to the maximum power point.