methods that can be used to reduce the fault current in the power system to an
acceptable leve l. These methods include: (a) network splitting, (b ) current limiting
reactors, (c) current limiting fuses and (d) fault current limiters [16,17].
4.3.1 Network splitting
If the network is split, often by opening substation bus-section circuit breakers, the
sources of short-circuit current are separated thus increasing the impedance
between the sources and the fault. This in turn reduces the fault current. The con-
sequence of network splitting is that the number of duplicate supply paths to a load
is reduced with potential reduction of reliability [17].
4.3.2 Current limiting reactors
A reactor can be placed in series with the generator circuit to increase the impedance
to the fault and so reduce the fault current. Despite a voltage drop and a power loss
associated with a reactor during normal operation, current limiting reactors are used
in practice due to their relatively low cost of implementation and maintenance.
4.3.3 Current limiting fuses
Current limiting fusegear consists of two parallel conductors: a main conductor and
a parallel fuse. Under normal operation, the load current flows through the main
conductor. During a fault, a tripping device disconnects the main conductor,
transferring the fault current to the parallel fuse with a high breaking capacity,
which limits the fault current during the initial rise of the first 50/60 Hz cycle [2].
4.3.4 Fault current limiters
Fault current limiters (FCLs) have a high impedance during a fault while having a
low impedance under normal operating conditions. Depending on the technology
used to obtain the required impedance characteristic, FCLs can be categorised into
three main groups: (a) superconducting fault current limiters (SFCL) [16,18,19],
(b) magnetic fault current limiters (MFCL) [20,21] and (c) static fault current
limiters [22,23].
There are two major types of the SFCL namely, resistive and inductive. The
resistive type is essentially a superconductor connected in series with the power
circuit [18,24,25]. The superconductor shows a negligible resistivity below a cri-
tical temperature (T
c
) and a critical current density (J
c
) (superconducting state), and
as soon as T
c
or J
c
are surpassed, the resistivity of the material increases rapidly
(normal state) [26]. The superconductor is located in a liquid nitrogen bath referred
to as ‘cryostat’. At liquid nitrogen temperature (77 K), the superconductor shows a
negligible resistance. During a fault as a high current passes through the super-
conductor, both current density and temperature increase above T
c
and J
c
. This in
turn takes the superconductor to its normal state, thus showing a high resistance in
series with the power line. This series resistor effectively limits the fault current.
Inductive SFCLs can broadly be divided into screened-core and saturated-core
types [18,25]. The screened-core design has a primary copper winding connected in
Fault currents and electrical protection 105