
1. Steady-state voltages, power flows and losses
A load flow study was carried out using the IPSA package and voltages; power
flows and losses were obtained for peak and minimum loading conditions. Figure
3.32 shows the load flow under peak and minimum loading conditions when DG is
importing VArs (0.95 leading power factor). It is clear from the diagram that during
the peak loading condition power flows from upstream to downstream via the line
between Buses 2 and 3. However, during the minimum loading condition excess
power in the distribution network is fed back to the grid.
Table 3.6 shows the voltage on busbars 3, 4, 5 and 6 and losses when a dis-
tributed generator is not connected, when it is operating at unity, 0.95 lagging
(exporting VArs
7
) and 0.95 leading (importing VArs) power factors. As the network
is weak (with a high impedance), under peak loading condition the voltage at some
busbars are below the limit (6%) when the distributed generator is not connected.
The distributed generator reduced the power flow in the line between Bus 2 and 3,
thus reducing the losses. When the distributed generator operates at unity power
Table 3.4 Circuit data
From bus To bus Length (km) R (pu/km) X (pu/km)
Bus 2 Bus 3 17.2
Bus 3 Bus 4 12.0
Bus 3 Bus 7 0.5 0.016250 0.034435
Bus 4 Bus 5 0.8
Bus 5 Bus 6 1.4
Table 3.5 Load data (all loads have a lagging power factor)
Busbar Peak Minimum
P (MW) Q (MVAr) P (MW) Q (MVAr)
3 2.0 0.48 0.25 0.06
4 2.0 0.48 0.25 0.06
5 2.4 0.56 0.30 0.07
6 3.2 0.80 0.40 0.10
Table 3.3 Transformer data
From bus To bus MVA rating Winding Reactance (%)
Bus 1 Bus 2 31.50 Yd1 10.5
Bus 7 DG 11.00 Yd1 8.8
7
Note that for a load, lagging power factor means it absorbs reactive power.
Distributed generators and their connection to the system 85