4.4 Protection of distributed generation
Traditionally, power-system protection has been designed assuming that central
generation feeds the distribution network and thus fault current always flows from
the hig her to the lower voltage levels. However, with the introduction of distributed
generation, both central and distributed generators feed current into a fault. This
multi-directional flow of fault currents requires the rechecking of existing protec-
tion coordination and reach.
A fault on the distribution system may result in a distributed generator being
disconnected together with some loads, thus creating a power island. As the fault
current from a distributed generator can be very low, a subsequent fault on the
islanded system may not be detected. In addition, depending on the design of the
network, the connection of the system neutral to earth (ground) may be lost during
islanding. Both conditions are undesirable. Additionally the creation of power islands
leads to difficulties with the use of auto-reclose on distribution networks as well as
posing safety issues for maintenance staff. Therefore, the protection philosophy of a
distributed generator should determine when it should stay connected, supporting the
main power system, and when it should be tripped off to ensure safety.
There is a well-known inconsistency in the way smaller generators are con-
sidered for connection to distribution and transmission networks, which will become
more and more important as the deployment of distributed generation increases.
Smaller generators that are connected to distribution networks are governed by the
requirements of IEEE 1547 (in the United States) [27] and G59 (in the United
Kingdom) [28]. IEEE 1547-2003 is applicable to all single or multiple distributed
generators of aggregated capacity of 10 MVA or less, and G59/1 applies to gen-
erators of 5 MW or less which are connected at 20 kV or below. These standards
require distributed generators to trip off during network faults/disturbances and not
to support power islands. In contrast for larger generators, G75 [29] allows islanded
operation to be considered, and the transmission Grid Codes require that non-
conventional generation (e.g. larger wind farms) connected to transmission systems
must remain stable and connected during network faults and support the operation
of the wider power system. As more and more small distributed generation is
connected to the power system, its aggregate effect will become important and the
consequences of it tripping during a network disturbance unacceptable. There have
already been instances reported in mainland Europe and Great Britain of a system
disturbance caused by network faults and loss of central generation being made
worse by the subsequent disconnection of distributed generation.
Figure 4.8 shows a distribution circuit with a distributed generator and typical
earthing arrangements used in the United Kingdom [30]. The protection philosophy
associated with the generator connection is explained by considering faults in dif-
ferent parts of the network.
1. For a phase or earth fault inside the distributed generator, fault currents flow
from the distribution network and that current is used to detect the fault.
2. For a fault at F
1
(i.e. on the connection between DG and the distribution net-
work), circuit breaker B removes the fault current flowing from the distribution
Fault currents and electrical protection 107