loss of mains and the generator then disconnected. Finally, the addition of dis-
tributed generation to a distribution network may alter the flows of network fault
current in subtle ways and so lead to maloperation of conventionally designed
distribution network protection systems.
When the insulation fails in a power system and a short-circuit fault occurs,
excessive currents, perhaps as high as 20 times the load current, will flow.
1
These
high currents may further damage the plant in which the insulation failure has
occurred or damage the other items of equipment through which the fault current
flows. These large fault currents can lead to fires or create hazardous voltages and
are not allowed to persist for more than a second or two. Electrical protection
schemes are used to isolate rapidly the faulty piece of plant while maintaining the
sound pieces of equipment in service in order to ensure minimum disruption of
supplies to customers. The large short-circuit currents disturb the operation of the
power system, particularly by depressing the voltage, and so faults are isolated
rapidly to maintain both voltage quality and stability of the system.
Different protection schemes have been developed to protect items of plant or
sections of the distribution network. It is conventional to divide the distribution net-
work into a number of zones to ensure discrimination is obtained and only the smallest
possible section of network is isolated for any fault. Most distribution network pro-
tection is designed to respond to fault current that is supplied by the large central
generators. These are electrically remote from faults on the distribution system and so
the magnitude of fault currents is determined mainly by the impedance of the trans-
mission and distribution networks. Thus, in traditional distribution network protection
design, the fault currents are well defined and quite easy to calculate. The addition of
generation located within the distribution network leads to more complex flows of
fault current that no longer comes only from the transmission network. In addition
many of the new types of generation use either induction generators or are connected to
the network through power electronic converters, whose ability to provide fault current
is determined both by the capability of the inverter and also by their control systems.
4.2 Fault current from distributed generators
All directly connected, spinning electrical machines (motors as well as generators)
supply fault current into a short circuit in the network. Too much short-circuit
current is dangerous, as it will over-s tress circuit breakers that try to break the
current and distort cables and other plant through which it passes. Too little short-
circuit current from generators is also of concern, as most protection systems on
distribution networks work by detecting the over-currents caused by faults, and so
will not work correctly with too little fault current.
If a distribution system is designed to provide good power quality (i.e. limited
variation in voltage with changes in load), it will have a high short-circuit level
2
1
The terms ‘short circuit’ and ‘fault’ are used interchangeably in this chapter.
2
The short circuit or fault level is the short-circuit or fault current that would flow in the event of a short
circuit or fault multiplied by the nominal prefault voltage at that point of the network.
96 Distributed generation