Derating
Refer
to
Section 14-6
for
derating engines
for
eleva-
tion
above
sea
level
and for
temperature. Derate
the
generator
1%
for
each
100 m
(3%/1000
ft)
above
900
m
(3000
ft).
Engine-Generator
Controls
The
engine instrument panel should never
be
mounted
on
the
engine
or on the
engine pad, because engine
vibration causes instruments
to
deteriorate.
The
instru-
ments
for the
engine should include:
• Oil
pressure
• Oil
temperature
•
Water temperature
•
Intake manifold pressure
and
vacuum
gauges
—
especially
for
large units.
A
battery-charging alternator
and
ammeter should
be
included. Require
safety
controls
for
engine shut-
down
to be
manually reset. Such controls should
include:
•
High water temperature
• Low oil
pressure
•
Overspeed.
The
following instruments
and
controls should
be
mounted
on the
generator control panel:
• An
ammeter with current transformers,
as
needed
• A
voltmeter with potential transformers,
as
needed
• An
ammeter/voltmeter phase selector switch
• A
frequency meter
(45 to 65 Hz)
• A
voltage-adjustment rheostat
• An
elapsed-time
meter
• An
annunciator
or
monitoring panel with
fault-
indicating
lights
for low oil
pressure, high water
temperature, overspeed, overcrank,
and
generator
undervoltage.
Standard annunciator panels
may be
specified
to
perform
all the
foregoing functions,
and
they usually constitute
a
much more economi-
cal
system than
a
hard-
wired
custom alarm system.
• A
fault
reset pushbutton
• A
generator output circuit breaker
• A
three-position
(manual-off-auto)
selector switch
• An
engine-start switch
• An
emergency stop pushbutton
• A
voltage regulator
• An
indicating-light test pushbutton.
Actuating
the
safety
devices must shut down
the
generator set, indicate
the
cause
of the
shut-down
by
lighting
the
appropriate indicating light,
and
provide
separate outputs
for the
remote alarm indication panel
and
the
computer.
Automatic
Transfer
Controls
Code
Requirements
Automatic transfer controls,
per NEC
701-7 (1981),
are
needed
for
legally required standby systems.
The
interconnection
of
normal
and
standby power sources
should
not be
possible
in any
mode
of
operation,
except where parallel operation
is
intended
and
suitable
automatic
or
manual synchronizing equipment
is
pro-
vided
per NEC
230-83.
In
pumping stations, automatic
transfer
control equipment
is
commonly installed,
except where portable generator sets
are to be
used.
Manual
Transfer
Switches
Manual
transfer switches
are
sometimes used with por-
table generating equipment.
Use
kVA-
(horsepower-)
rated, quick-make/quick-break, heavy-duty switches
or
mechanically interlocked circuit breakers.
If the
trans-
fer
switch
is
part
of the
station service equipment,
it
must
be
UL-listed
as
service equipment
or
better,
and it
must
have
a
separate UL-listed service disconnect (cir-
cuit
breaker) ahead
of it in a
separate enclosure.
Automatic
Transfer
Switches
(ATS)
Complete automatic transfer switches
are
available
in
suitable enclosures (e.g., NEMA
1) as
well
as in
open
style
for
installation
in
motor control centers. They
must conform
to all of the
requirements
of UL
1008
and
be so
listed
and
labeled. Bypass isolation switches
(that
allow
the ATS to be
removed
for
repairs)
are
desirable
for
avoiding shutdowns
for
repairs.
Automatic transfer switches include
a
switching
element, relays,
and
controls
and are
available
in
these
forms:
•
Molded-case
circuit breakers
•
Contactors
•
Double-throw switches.
Automatic
transfer switches should have
the
follow-
ing
ratings:
•
Continuous rating, which
is the
current rating
on a
24-hr basis.
•
Inrush rating, which
is the
ability
to
close
a
circuit
with
high inrush currents with minimum contact
bounce
and
welding.
•
Interrupting rating, which
is the
load- (not necessar-
ily
fault-)
interrupting ability under
the
worst condi-