•
Temperature rise
•
Basic impulse level (BIL)
•
K-rating,
if
applicable. K-rated transformers
are
specially designed
to
resist
the
heating
effects
of
currents with harmonic frequencies (multiples
of
rated frequency).
In
pumping stations, adjustable-
speed
motor controllers
are the
major source
of
har-
monic currents.
The
desired construction details should include:
•
Insulation
medium
—
dry
or
liquid type
•
Indoor
or
outdoor service
•
Accessories
—
monitoring
and
safety
devices, light-
ning
arrestors
•
Type
and
location
of
terminating facilities
•
Sound-level limitations
(if
any)
•
Manual
or
automatic load
tap
changing
•
Grounding requirements
•
Cooling
or
provisions
for
future
cooling
•
Energy conservation features.
In
pumping stations
of
more
than several
kVA
full-load
rating,
the
transformers connected
to the
utility
are
ordinarily three-phase units. Some utilities
serve small three-phase pumping stations
at 240 V
using
three pole-mounted single-phase transform-
ers.
Two
such transformers connected
in
open delta
are
sometimes used,
but
this practice should
not be
tolerated
for
fully
loaded pumps, because
the
phase
voltages
are
somewhat unbalanced
and
cause exces-
sive
phase currents
and
motor overheating.
In
larger
installations,
the
transformer
may be the
property
of
the
station owner
and may be
part
of the
switchgear
lineup.
Large transformer ownership
can be
negoti-
ated with
the
utility.
Single-phase, dry-type transformers
are
com-
monly
used
to
supply
120 V
convenience recepta-
cles, lighting,
and
small power loads, such
as
control
and
instrument
and
computer power. Three-phase
transformers
with
a
delta-wye winding connection
shown
in
Figure 8-10
are
also widely used.
The wye
connection
can
supply both three-phase
and
single-
phase loads simultaneously.
The
neutral
is
grounded
and
results
in a
uniform
potential relative
to
ground
in
all
phases.
For
long-term variations
in
supply voltage
or for
growth
in
plant load, power transformers should have
two
2.5% primary taps above normal
and two
2.5%
taps
below normal. These primary winding taps
are
usually
specified
for
de-energized reconnection.
The
impedance rating
of a
transformer
is
usually
given
in
percent
of
full
load ratings,
and it is
ordi-
narily
specified
at 5 to 8%.
This impedance limits
the
current
that would
flow in the
primary
and
secondary
systems
of the
transformer
if a
short circuit occurs
in
the
secondary system
or at the
terminals
of the
trans-
former.
Therefore,
the
impedance
(in
conjunction with
the
supply system's available short circuit current)
determines:
(1)
the
required interrupting ratings
of the
load switching devices
and
fault
current interrupting
devices
(fuses
and
circuit breakers)
and (2) the
brac-
ing
required
in
buswork.
But the
higher
the
imped-
ance,
the
higher
the
voltage regulation, particularly
during motor starting. Hence, carefully strike
a
bal-
ance
between available short circuit current
and
volt-
age
regulation.
Many
pole-mounted
and
pad-mounted transform-
ers
furnished
by the
utilities have
low
impedances,
such
as 3%, and
thus they allow relatively higher
fault
current during short circuit conditions than
do
higher
impedance units.
Low
impedance transformers
can
result
in
more expensive switchgear,
and
thus
the
cheaper low-impedance transformer
may be
poor
in
overall economy. System voltage drop during motor
starting
is,
however, less with
low
impedance trans-
formers.
Transformers
are
rated
in kVA at a
specific temper-
ature determined
by
winding resistance measurements
in
accordance
with NEMA standards.
The
transformer
temperature rating
is a
function
of the
insulation sys-
tem
used.
The
effects
of
excessive temperature rise
on
insulation
in
transformers
and
electric motors
are
identical.
See
Section 13-9
and
Table 13-2
for
more
detail.
If
proper allowance
has
been made
in the
specifi-
cations
for a
transformer, plant load increases
may
be
accommodated
by the
addition
of
cooling
fans
and/or
an oil
circulation heat exchanger system
to
allow
the
transformer
to
withstand
a
larger load
current safely.
Switches
The
types
of
switches normally applied
in
power cir-
cuits
include
the
following:
•
Disconnecting switches
•
Load interrupter
(or
load break) switches
•
Safety switches
•
Control switches.
A
disconnecting switch
is
used
for
isolating
a
circuit
or
equipment
from
the
source
of
power.
It
has no
interrupting rating
and is
intended only
for
operation after
the
circuit
has
been de-energized
by
other means.
Load interrupter switches
are
intended
for
operat-
ing
on
circuits
of 600
volts
or
above. They
are of air or