AUTO RECLOSE FOR ONE-AND A HALF BREAKER OR
Line protection
for worldwide cooperation
137
BA THS / BU Transmission Systems and Substations
LEC Support Programme
- Energizing of a line onto a fault. When a line is closed onto a fault the
Auto recloser is blocked to prevent unnecessary disturbances in the
power network. The chance of a persistent fault is high as the line has
not been carrying load and is therefor not a part of “normal conditions”.
- Auto-reclosing onto a persistent fault. An unsucessful auto reclosing
means that the fault probably is persistent. The auto-recloser is then
blocked to prevent new attempts. Solutions with several attempts how-
ever exists but the breaker duty cycle must then be carefully checked.
- “Breaker not ready” is used to block the auto-recloser. The breaker is
then not ready to perform any attempt and the breaker can not be auto-
matic reclosed.
- PLC (or communication channel) out of service must be connected to
block the Auto recloser if a quick auto reclose attempt is used. The fault
has not surely been cleared from the remote end and an auto reclose
might therefor not be successful.
5. AUTO RECLOSE FOR ONE-AND A HALF
BREAKER OR RING BUSBAR SCHEMES.
Auto reclosing of transmission line circuit-breakers is somewhat
more complicated in One- and a half breaker, 2–breaker and
Ring busbar stations than in simpler stations with a One line -
One breaker arrangement. At a line fault two CB’s shall be tripped
and reclosed at each end of the line and some coordination is re-
quired. In addition one circuit breaker (tie breaker) is shared by
two circuits in One- and a half breaker and Ring busbar stations.
A standardized Auto reclosing scheme designed by ABB com-
bines flexibility with some particular features:
- High-speed or delayed Auto reclosing.
- Single-pole an/or three-pole Auto reclosing with independent setting of
dead times.
- Synchronism check feature as an option. It can be combined with de-
layed or high-speed three pole Auto reclosing.
- Cooperation with single- or duplicate line relays.
- Adapted to communicating line relays or Distance relays with overreach
of zone 1 before Auto reclosing.