SYNCHRO CHECK DEVICE
Line protection
for worldwide cooperation
151
BA THS / BU Transmission Systems and Substations
LEC Support Programme
- a moderate operation time, typically less than 0.2-0.5 seconds.
6.3 HIGH-SPEED AUTO RECLOSING WITH SYN-
CHRONISM CHECK
In power systems where the stability is strained under periods of
high load, one would like to reclose quickly in order to improve the
stability. If the parallel interconnection is unreliable, for instance
in a system like fig. 29b or 29c, it can be risky to perform a
high-speed reclosing without synchronism check. One can then
be forced to refrain from reclosing, rely on single pole auto-re-
closing at single-phase faults or take a chance with delayed au-
to-reclosing.
In the latter case the Auto reclosing may be blocked at high loads,
which is unfortunate, especially if a high-speed reclosing could
have saved the stability. In such cases it would be preferable to
adopt high-speed reclosing with dead line check and synchro-
nism check.
When a parallel line is in service Auto-reclosing can then be per-
formed. On the other hand, when the parallel circuit is out of ser-
vice, the reclosing will be blocked as the synchronism is most
likely lost during the dead time.
Auto-reclosing with dead line and synchronism check can in
many cases be applied also for lines near a power station.
By choosing to energize the line from the remote end the strain
at reclosing into a persistent fault will be moderate. Because the
remote end is retripped at a persistent fault, the end near the
power station will not be reclosed. Only after a successful line re-
energizing the synchronism check conditions will be met and the
line reclosing completed.
At a controlled high-speed Auto reclosing the dead line check is
made during the dead interval of 0.4-1.0 seconds and a time for
dead-line check of 0.2 seconds can be allowed. The synchronism
check is made after line reenergizing and the check should be
quick to avoid unnecessary delay of the reclosing. It must howev-
er wait about 0.1 seconds for a possible retripping of the remote
end. Assuming a dead interval of 0.4 seconds, a synchronism
check time of 0.2 seconds and time for circuit-breaker closing of