MEASURING PRINCIPLES
122
BA THS / BU Transmission Systems and Substations
LEC Support Programme
where a blocking signal is sent for “start” but not “forward” should,
as a general principle, never be used together with a relay with a
true reverse directional element sending the blocking signal.
The using of Permissive schemes or Blocking schemes in the
system depends on the preference for Security or Dependability.
A Blocking scheme will be Dependable, i. e. it will operate for an
internal fault also with a failing communication link, but it has a
lower security as it can maloperate for an external fault due to a
failing communication link. The Permissive scheme has the op-
posite behavior. The advantage with the blocking scheme is that
communication signals are sent on healthy lines whereas on per-
missive scheme the communication signals are sent over a faulty
line.
Reasons for incorrect impedance measurement
To enable a correct impedance measurement the measured volt-
age must be a function of only the locally measured current “I
A
”
and the impedance at the fault. This is naturally not always the
case in double-end infeed and meshed transmission networks.
REMOTE FAULTS
If a fault occurs on an outgoing line in the re-
mote substation where the own line will feed fault current “I
f1
”,
see fig 13, the other lines in the remote station will also contribute
with the fault currents “I
f2
” and “I
f3
”. The measured impedance at
the local station will then be as in the figure and the measured im-
pedance at the fault will seem much higher than the “true” imped-
ance to the fault. The relays will thus get an apparent underreach.
This means that, in practice the possibility to get a “remote
back-up” in a transmission network is limited. A local back-up
must therefor normally be provided.