REQUIREMENTS ON LINE PROTECTION
102
BA THS / BU Transmission Systems and Substations
LEC Support Programme
The consequences of a fault must be limited and the power sup-
ply to the consumers secured. The protection system must there-
for be capable of distinguish between an external and an internal
faults also for low magnitude faults on a heavy loaded object, or
for parallel objects where close to similar parameters exist for
both healthy and faulty object.
Requirement on selectivity
In order to fulfil these requirements the protection relays has to
be able to distinguish between the normal operating condition of
the protected object and an electrical fault i.e. give a reliable fault
detection unaffected by normal operating conditions such as
load, inrush currents etc. In some cases it is also required that
the protection relay must be able to detect also other abnormal
operating conditions such as overexcitation, overload, broken
conductor etc. These aren’t electrical faults but may still damage
the protected object or other apparatus in the network. Since
power apparatus in many applications have to operate near their
rated limits it is important that this part of the protection system
exactly can distinguish between permissible and none permissi-
ble operating conditions.
Electrical faults are normally required to be cleared instanta-
neously. Other abnormal operating conditions, can be accepted
to result in time delayed action.
Dependability and security are contradictory to each other but
have to be evaluated together due to the linking of the two quali-
ties. In redundant protection schemes the whole scheme has to
be evaluated not only the individual relays.
To achieve maximum dependability combined with maximum se-
curity the communication demands shall be at minimum. Wide
band transmission is not only expensive it will also be more ex-
posed to interference. The latter is apparent when power line car-
rier is used. The communication demand is therefore linked with
dependability and security.