DESIGN OF EARTH FAULT PROTECTION RELAYS
80
BA THS / BU Transmission Systems and Substations
LEC Support Programme
SELECTIVE EARTH FAULT PROTECTION With the relay technique of
today selective earth fault protection relays can be used in most
networks (independent of system earthing). Directional protec-
tion relays, with sensitivities of a few Ampere primary operates on
the transient and detects the earth fault even with high fault resis-
tance. Modern Protection relays which measures fundamental or
high frequency can sucessfully be used at earth fault protection.
Historically the using of selective earth faults was an important
reason to choose a high earth fault current. In directly earthed
transmission network that generates earth fault current from
many points, the using of selective earth fault protection will be
more complicated and require direction, inverse time character-
istics and calculations on current distribution in all possible fault
situations, to select settings which will give selectivity.
APPARATUSES INSULATION TO EARTH In an effectively (direct)
earthed network a graded insulation can be utilized. This gives
cost savings of 10-15% for voltages of type 130 kV. Regarding
the apparatus prices at higher voltage levels a fully insulated ze-
ro-point and the requirements on the insulation becomes impor-
tant. At voltages above 130-170 kV, nothing else but direct
earthing is used.
8. DESIGN OF EARTH FAULT PROTECTION
RELAYS
An earth fault protection relay should be constructed to interact
well with the system earthing method chosen for the network.
The system earthing shouldn’t be negatively affected by the re-
quirements on the earth fault protection relays. In some cases,
the system earthing can be chosen to make relays work more
safely.
A few of these cases will be penetrated below and Earth fault pro-
tection is further discussed in a separate section.
8.1 PARALLEL RESISTORS FOR THE RESONANCE