MEASURING PRINCIPLES
112
BA THS / BU Transmission Systems and Substations
LEC Support Programme
A small arc resistance “R
f
”
exists in the fault. The arc resistance
R
arc
can according to Warrington be calculated as:
R
arc
= 28700 * a / I
1.4
where:
a is the length of the arc in m i. e. the length of the insulator for
earth fault and the phase distance at phase faults.
I is the fault current through the fault resistance in A.
During earth faults, the tower foot resistance also will occur in the
fault loop. The Distance protection relays must therefor cover an
area of the line impedance, plus the fault resistance as indicated
in the figure. Tower foot resistances should normally be kept be-
low 10 Ω. Top lines connecting towers together will give parallel
path and lower the tower foot resistance.
In some areas as high values as 50 Ω can exist and special pre-
cautions to protect against earth faults can then be necessary.
The vector “Z
b
” shows the location of the load impedance. Nor-
mally the load impedance is close to “cos Ø=1”. The Distance
protection relays must be able to distinguish between fault and
load conditions even if the impedances are of the same size.
The detection of the forward direction is an important function for
a Distance protection. The directional sensitivity must be abso-
lute and serve down to zero voltage.
The back-up function is simply achieved, by an extension of the
impedance reach with time steps (see figure 8).
For normal lines with a distance longer than approximately 15 km
the first step of impedance, is underreaching the line end with ab-
solute selectivity covering about 80% of the line. The 80% reach
is selected due to errors in distance measurement due to Current
and Voltage transformer errors, relay accuracy and influence
from the system as described further below.
A fault at “F1” will be tripped instantaneously from both protection
“A” and “B”. Normal operating time in modern Distance protec-
tion relays is 15-30ms. Operating time will be dependent on
source to impedance ratio, setting, fault resistance, fault position,
CVT filter and the point of wave at which the fault occurs.