
15 Inverters 379
TABLE 15.6 Zero SV for minimum switching
frequency in CSI and sequence
i
i
,
i
i+1
,
i
z
Sector
i
i
i
i+1
i
z
➀
i
6
i
1
i
7
➁
i
1
i
2
i
9
➂
i
2
i
3
i
8
➃
i
3
i
4
i
7
➄
i
4
i
5
i
9
➅
i
5
i
6
i
8
the possible transitions that could be found in Sector ➁.
It can be seen that the zero vector
i
9
should be chosen to
minimize the switching frequency. Table 15.6 gives a sum-
mary of the zero space vector to be used in each sector in
order to minimize the switching frequency. However, should
be noted that Table 15.6 is valid only for the sequence
i
i
,
i
i+1
,
i
z
. Another sequence will require reformulating the zero
space-vector selection algorithm.
C. The Normalized Sampling Frequency
As in VSIs modulated by a SV approach, the normalized sam-
pling frequency f
sn
should be an integer multiple of 6 to min-
imize uncharacteristic harmonics. As an example, Fig. 15.35
shows the relevant waveforms of a CSI SVM for f
sn
= 18 and
ˆ
i
c
= 0.8. Figure 15.35 also shows that the first set of relevant
harmonics load line current are at f
sn
.
15.4.5 DC Link Voltage in Three-phase CSIs
An instantaneous power balance indicates that
v
i
(t) · i
i
(t) = v
an
(t) · i
oa
(t) + v
bn
(t) · i
ob
(t) + v
cn
(t) · i
oc
(t)
(15.60)
where v
an
(t), v
bn
(t), and v
cn
(t) are the phase filter voltages
as shown in Fig. 15.36. If the filter is large enough and a
relatively high switching frequency is used, the phase voltages
become nearly sinusoidal balanced waveforms. On the other
hand, if the ac output currents are considered sinusoidal and
the dc link current is assumed constant i
i
(t) = I
i
, Eq. (15.60)
can be simplified to
v
i
(t)=
1
I
i
√
2V
on
sin(ωt)·
√
2I
o1
sin(ωt −φ)
+
√
2V
on
sin(ωt −120
◦
)·
√
2I
o1
sin(ωt −120
◦
−φ)
+
√
2V
on
sin(ωt −240
◦
)·
√
2I
o1
sin(ωt −240
◦
−φ)
(15.61)
where V
on
is the rms ac output phase voltage, I
o1
is the rms
fundamental line current, and φ is an arbitrary filter-load
angle. Hence, the dc link voltage expression can be further
simplified to the following:
v
i
(t) = 3
I
o1
I
i
V
on
cos(φ) =
√
3
I
o1
I
i
V
o
cos(φ) (15.62)
where V
o
=
√
3V
on
is the rms load line voltage. The resulting
dc link voltage expression indicates that the first line-current
harmonic I
o1
generates a clean dc current. However, as the
load line currents contain harmonics around the normalized
sampling frequency f
sn
, the dc link current will contain har-
monics but around f
sn
as shown in Fig. 15.35h. Similarly, in
carrier-based PWM techniques, the dc link current will contain
harmonics around the carrier frequency m
f
(Fig. 15.27).
In practical implementations, a CSI requires a dc current
source that should behave as a constant (as required by PWM
CSIs) or variable (as square-wave CSIs) current source. Such
current sources should be implemented as separate units and
they are described earlier in this book.
15.5 Closed-loop Operation of Inverters
Inverters generate variable ac waveforms from a dc power sup-
ply to feed, for instance, ASDs. As the load conditions usually
change, the ac waveforms should be adjusted to these new con-
ditions. Also, as the dc power supplies are not ideal and the
dc quantities are not fixed, the inverter should compensate for
such variations. Such adjustments can be done automatically
by means of a closed-loop approach. Inverters also provide
an alternative to changing the load operating conditions (i.e.
speed in an ASD).
There are two alternatives for closed-loop operation the
feedback and the feedforward approaches. It is known that
the feedback approach can compensate for both the pertur-
bations (dc power variations) and the load variations (load
torque changes). However, the feedforward strategy is more
effective in mitigating perturbations as it prevents its negative
effects at the load side. These cause-effect issues are analyzed in
three-phase inverters in the following, although similar results
are obtained for single-phase VSIs.
15.5.1 Feedforward Techniques in Voltage
Source Inverters
The dc link bus voltage in VSIs is usually considered a constant
voltage source v
i
. Unfortunately, and due to the fact that most
practical applications generate the dc bus voltage by means of
a diode rectifier (Fig. 15.37), the dc bus voltage contains low-
order harmonics such as the sixth, twelfth, ...(due to six-pulse