324 Electrical Circuit Theory and Technology
Further problems on the e.m.f. equation may be found in Section 20.16,
problems 13 to 16, page 345.
20.5 Transformer
on-load phasor diagram
If the voltage drop in the windings of a transformer are assumed negli-
gible, then the terminal voltage V
2
is the same as the induced e.m.f. E
2
in
the secondary. Similarly, V
1
D E
1
. Assuming an equal number of turns
on primary and secondary windings, then E
1
D E
2
, and let the load have
a lagging phase angle
2
.
In the phasor diagram of Figure 20.4, current I
2
lags V
2
by angle
2
.
When a load is connected across the secondary winding a current I
2
flows
in the secondary winding. The resulting secondary e.m.f. acts so as to tend
to reduce the core flux. However this does not happen since reduction of
the core flux reduces E
1
, hence a reflected increase in primary current I
0
1
occurs which provides a restoring mmf. Hence at all loads, primary and
secondary mmf’s are equal, but in opposition, and the core flux remains
constant. I
0
1
is sometimes called the ‘balancing’ current and is equal, but
in the opposite direction, to current I
2
as shown in Figure 20.4. I
0
, shown
at a phase angle
0
to V
1
, is the no-load current of the transformer (see
Section 20.3).
The phasor sum of I
0
1
and I
0
gives the supply current I
1
and the phase
angle between V
1
and I
1
is shown as
1
.
Figure 20.4
Problem 12. A single-phase transformer has 2000 turns on the
primary and 800 turns on the secondary. Its no-load current is 5 A
at a power factor of 0.20 lagging. Assuming the volt drop in the
windings is negligible, determine the primary current and power
factor when the secondary current is 100 A at a power factor of
0.85 lagging.
Let I
0
1
be the component of the primary current which provides the
restoring mmf. Then
I
0
1
N
1
D I
2
N
2
i.e., I
0
1
2000 D 100800
from which, I
0
1
D
100800
2000
D 40 A
If the power factor of the secondary is 0.85
then cos
2
D 0.85, from which,
2
D arccos0.85 D 31.8
°
If the power factor on no-load is 0.20,
then cos
0
D 0.2and
0
D arccos0.2 D 78.5
°
In the phasor diagram shown in Figure 20.5, I
2
D 100 A is shown at an
angle of
2
D 31.8
°
to V
2
and I
0
1
D 40 A is shown in anti-phase to I
2
.
Figure 20.5