Network Protection & Automation Guide
17-18
potentially damaging rotor vibration. Detection of such an
electrical fault is possible using a probe consisting of a coil
placed in the airgap. The flux pattern of the positive and
negative poles is measured and any significant difference in
flux pattern between the poles is indicative of a shorted turn or
turns. Automated waveform comparison techniques can be
used to provide a protection scheme, or the waveform can be
inspected visually at regular intervals. An immediate
shutdown is not normally required unless the effects of the
fault are severe. The fault can be kept under observation until
a suitable shutdown for repair can be arranged. Repair will
take some time, since it means unthreading the rotor and
dismantling the winding.
Since short-circuited turns on the rotor may cause damaging
vibration and the detection of field faults for all degrees of
abnormality is difficult, the provision of a vibration a detection
scheme is desirable – this forms part of the mechanical
protection of the generator.
17.15.4 Protection Against Diode Failure
A short-circuited diode will produce an a.c. ripple in the exciter
field circuit. This can be detected by a relay monitoring the
current in the exciter field circuit, however such systems have
proved to be unreliable. The relay would need to be time
delayed to prevent an alarm being issued with normal field
forcing during a power system fault. A delay of 5-10 seconds
may be necessary.
Fuses to disconnect the faulty diode after failure may be fitted.
The fuses are of the indicating type, and an inspection window
can be fitted over the diode wheel to enable diode health to be
monitored manually.
A diode that fails open-circuit occurs less often. If there is
more than one diode in parallel for each arm of the diode
bridge, the only impact is to restrict the maximum continuous
excitation possible. If only a single diode per bridge arm is
fitted, some ripple will be present on the main field supply but
the inductance of the circuit will smooth this to a degree and
again the main effect is to restrict the maximum continuous
excitation. The set can be kept running until a convenient
shutdown can be arranged.
17.15.5 Field Suppression
The need to rapidly suppress the field of a machine in which a
fault has developed should be obvious, because as long as the
excitation is maintained, the machine will feed its own fault
even though isolated from the power system. Any delay in the
decay of rotor flux will extend the fault damage. Braking the
rotor is no solution, because of its large kinetic energy.
The field winding current cannot be interrupted
instantaneously as it flows in a highly inductive circuit.
Consequently, the flux energy must be dissipated to prevent an
excessive inductive voltage rise in the field circuit. For
machines of moderate size, it is satisfactory to open the field
circuit with an air-break circuit breaker without arc blow-out
coils. Such a breaker permits only a moderate arc voltage,
which is nevertheless high enough to suppress the field current
fairly rapidly. The inductive energy is dissipated partly in the
arc and partly in eddy-currents in the rotor core and damper
windings.
With generators above about 5MVA rating, it is better to
provide a more definite means of absorbing the energy without
incurring damage. Connecting a ‘field discharge resistor’ in
parallel with the rotor winding before opening the field circuit
breaker will achieve this objective. The resistor, which may
have a resistance value of approximately five times the rotor
winding resistance, is connected by an auxiliary contact on the
field circuit breaker. The breaker duty is thereby reduced to
that of opening a circuit with a low L/R ratio. After the breaker
has opened, the field current flows through the discharge
resistance and dies down harmlessly. The use of a fairly high
value of discharge resistance reduces the field time constant to
an acceptably low value, though it may still be more than one
second. Alternatively, generators fitted with static excitation
systems may temporarily invert the applied field voltage to
reduce excitation current rapidly to zero before the excitation
system is tripped.
17.16 LOSS OF EXCITATION PROTECTION
Loss of excitation may occur for a variety of reasons. If the
generator was initially operating at only 20%-30% of rated
power, it may settle to run super-synchronously as an
induction generator, at a low level of slip. In doing so, it will
draw reactive current from the power system for rotor
excitation. This form of response is particularly true of salient
pole generators. In these circumstances, the generator may be
able to run for several minutes without requiring to be tripped.
There may be sufficient time for remedial action to restore the
excitation, but the reactive power demand of the machine
during the failure may severely depress the power system
voltage to an unacceptable level. For operation at high initial
power output, the rotor speed may rise to approximately 105%
of rated speed, where there would be low power output and
where a high reactive current of up to 2.0p.u. may be drawn
from the supply. Rapid automatic disconnection is then
required to protect the stator windings from excessive current
and to protect the rotor from damage caused by induced slip
frequency currents.
© 2011 Alstom Grid. Single copies of this document may be filed or printed for personal non-commercial use and must include this
copyright notice but may not be copied or displayed for commercial purposes without the prior written permission of Alstom Grid.