Network Protection & Automation Guide
17-12
case, the VT must be capable of carrying residual flux, and this
prevents the use of 3-limb types. If the third harmonic voltage
is measured at the generator star point, an undervoltage
characteristic is used. An overvoltage characteristic is used if
the measurement is taken from the generator line VT. For
effective application of this form of protection, there should be
at least 1% third harmonic voltage across the generator neutral
earthing impedance under all operating conditions.
A problem encountered is that the level of third harmonic
voltage generated is related to the output of the generator.
The voltage is low when generator output is low. In order to
avoid maloperation when operating at low power output, the
relay element can be inhibited using an overcurrent or power
elements (kW, kVAr or kVA) and internal programmable logic.
17.8.4.2 Use of Low-Frequency Voltage Injection
Another method for protecting the entire stator winding of a
generator is to deploy signal injection equipment to inject a low
frequency voltage between the stator star point and earth. An
earth fault at any winding location will result in the flow of a
measurable injection current to cause protection operation.
This form of protection can provide earth fault protection when
the generator is at standstill, prior to run-up. It is also an
appropriate method to apply to variable speed synchronous
machines. Such machines may be employed for variable
speed motoring in pumped-storage generation schemes or for
starting a large gas turbine prime mover.
17.9 OVERVOLTAGE PROTECTION
Overvoltages on a generator may occur due to transient surges
on the network, or prolonged power frequency overvoltages
may arise from a variety of conditions. Surge arrestors may be
required to protect against transient overvoltages, but relay
protection may be used to protect against power frequency
overvoltages.
A sustained overvoltage condition should not occur for a
machine with a healthy voltage regulator, but it may be caused
by the following contingencies:
x defective operation of the automatic voltage regulator
when the machine is in
isolated operation
x operation under manual control with the voltage
regulator out of service. A sudden variation of the load,
in particular the reactive power component, will give
rise to a substantial change i
n voltage because of the
large voltage regulation inherent in a typical alternator
x sudden loss of load (due to tripping of outgoing feeders,
leaving the set isolated or feeding a very small load)
may cause a su
dden rise in terminal voltage due to the
trapped field flux and/or overspeed
Sudden loss of load should only cause a transient overvoltage
while the voltage regulator and governor act to correct the
situation. A maladjusted voltage regulator may trip to manual,
maintaining excitation at the value prior to load loss while the
generator supplies little or no load. The terminal voltage will
increase substantially, and in severe cases it would be limited
only by the saturation characteristic of the generator. A rise in
speed simply compounds the problem. If load that is sensitive
to overvoltages remains connected, the consequences in terms
of equipment damage and lost revenue can be severe.
Prolonged overvoltages may also occur on isolated networks,
or ones with weak interconnections, due to the fault conditions
listed earlier.
For these reasons, it is prudent to provide power frequency
overvoltage protection, in the form of a time-delayed element,
either IDMT or definite time. The time delay should be long
enough to prevent operation during normal regulator action,
and therefore should take account of the type of AVR fitted and
its transient response. Sometimes a high-set element is
provided as well, with a very short definite-time delay or
instantaneous setting to provide a rapid trip in extreme
circumstances. The usefulness of this is questionable for
generators fitted with an excitation system other than a static
type, because the excitation will decay in accordance with the
open-circuit time constant of the field winding. This decay can
last several seconds. The relay element is arranged to trip both
the main circuit breaker (if not already open) and the
excitation; tripping the main circuit breaker alone is not
sufficient.
17.10 UNDERVOLTAGE PROTECTION
Undervoltage protection was historically rarely fitted to
generators. It is sometimes used as an interlock element for
another protection function or scheme, such as field failure
protection or inadvertent energisation protection, where the
abnormality to be detected leads directly or indirectly to an
undervoltage condition. A transmission system undervoltage
condition may arise when there is insufficient reactive power
generation to maintain the system voltage profile and the
condition must be addressed to avoid the possible
phenomenon of system voltage collapse. However, it should
be addressed by the deployment of ’system protection’
schemes. The generation should not be tripped. The greatest
case for undervoltage protection being required would be for a
generator supplying an isolated power system or to meet the
public Utility demands for connection of embedded generation
(see Section 17.21).
In the case of generators feeding an isolated system,
undervoltage may occur for several reasons, typically
overloading or failure of the AVR. In some cases, the
© 2011 Alstom Grid. Single copies of this document may be filed or printed for personal non-commercial use and must include this
copyright notice but may not be copied or displayed for commercial purposes without the prior written permission of Alstom Grid.