PRIMARY TREATMENT 21-11
c. The elevation of the bottom of the tank is
Elevation of bottom mmm280 00 4 3 0 3 27...5540. m
d. Elevation of groundwater table that is incipient to flotation:
Elev mm m.. . .275 40 0 72 276 12
Comment. Because of soil friction and the mass of the tank walls, the groundwater table will
have to be somewhat higher than shown by this calculation to cause flotation of the tank.
Circular Sedimentation Basin Design
Because center feed basins are the most commonly used systems, only they are discussed here.
The specific elements to be considered are the diameter, depth, flow balancing, inlet configura-
tion, sludge removal, and scum removal.
Diameter. Overflow rate is the controlling variable in d
etermining both the area and the diam-
eter of a circular clarifier. Although tanks up to 100 m in diameter have been built, generally they
are limited to about 50 m because of the effects of wind (Tekippe, 2006). Metcalf & Eddy (2003)
reported ranges from 3 to 60 m with typical values of 12 to 45 m.
Depth. Depths are measured as side water depth.
With a sloped floor, the depth at the center of
the tank will be deeper. Most floors have a constant floor slope of 1 on 12 (vertical:horizontal).
The origin of this particular slope is uncertain, but it has received widespread use for decades
(Tekippe, 2006).
The tanks must be deep enough to accommodate mechanical equipment for sludge removal,
store settled
solids, avoid scour, and avoid carryover of solids in the effluent. Excessive depth is to
be avoided to prevent anaerobic conditions. Shallower tanks may be acceptable with continuous
sludge removal.
Theoretically, removal efficiency should increase with depth because the opportunity
for
particle contact and flocculation increase with depth. In practice, it has been found that depth and
overflow rate are intimately related. To achieve the highest efficiency, deeper tanks with lower
overflow rates are required (Tekippe, 2006). Reported depths have ranged from 3 to 5 m with
a typical value of 4.3 m (Metcalf & Eddy, 2003; WEF, 1998). Current trends favor the use of
deeper tanks (Wahlberg, 2006).
Common practice is to provide a freeboard of 0.5 to 0.7 m.
Splitter Box. When multiple units are in service, the flow must be split so that both the hydraulic
load and the solids load are in proportion to the design limits of the tank. Upflow distribution
structures ( splitting boxes ) with fixed weirs can be used to provid
e identical flow to identical
multiple units ( Figure 21-6 ). Weir lengths are adjusted in proportion to the surface area if the units
have different surface areas. When the settling tanks have different side water depths, the weir
lengths are adjusted so that they are proportional to the volume of the tanks. When both the
surface area and depth of the tanks differ, the weir length is adjusted in proportion to the volu
me
of the tanks. To minimize turbulent conditions, the upflow velocity into the flow splitting box
should be less than 0.3 m/s at peak flow. The top of the discharge should be sufficiently below