
UNIT 47 Refrigeration Controls 453
refrigeration systems operate at lower temperatures
and must employ some method for defrosting the
evaporator.
Many refrigeration systems, such as open freez-
ers in supermarkets, are intended to operate inside
an air conditioned building. It is this operating
environment that can create some special problems.
The cold ambient air temperature in winter or the
cool air inside an air conditioned building can cause
the compressor head pressure to drop below a point
such that the pressure differential between the high
and low side of the system is insuf cient for the unit
to operate ef ciently. When this is the case, some
method must be employed to raise the tempera-
ture of the condenser and permit the compressor
head pressure to increase. Some common ways of
accomplishing this are fan cycle control, shutters,
and condenser ooding. Refrigeration and air condi-
tioning units that employ water-cooled condensers
control the ow of cooling water to maintain head
pressure.
CONDENSER FLOODING
Condenser ooding is accomplished by placing
a pressure operated valve in the refrigerant line
between the condenser and metering valve. More
than one method can be employed to accomplish
this. Flooding the condenser with liquid refrigerant
COMPRESSOR
CONDENSER
HEAD PRESSURE
CONTROL VALVE
EVAPORATOR
METERING VALVE
RECEIVER
has the effect of covering the condenser with a plas-
tic blanket. This causes an increase in condenser
temperature and a corresponding increase in head
pressure. To accomplish condenser ooding, the
unit must contain enough liquid refrigerant to ood
the condenser. This calls for a large charge of refrig-
erant and some means of storing it. Units intended
to use condenser ooding contain a receiver to hold
the excess refrigerant.
Nonadjustable Head
Pressure Valve
Figure 47–1 illustrates the connection of a nonad-
justable head pressure control valve. A line drawing
of the valve is shown in Figure 47–2. The valve’s
main port is between the condenser and receiver.
As long as receiver pressure remains above a certain
level the bypass between discharge and receiver por-
tions of the valve are closed. If the receiver pressure
should drop, such as would be the case with low
ambient temperature, the spring loaded valve over-
comes the receiver pressure and hot gas begins to
ow through the discharge portion of the valve. Low
receiver pressure also causes the valve to decrease
the ow from the condenser, causing refrigerant
to backup in the condenser. This has the effect of
decreasing the surface area of the condenser caus-
ing an increase in temperature and a corresponding
Figure 47–1
The head pressure control valve meters the fl ow of refrigerant through the condenser. (Source: Delmar/Cengage Learning)