CURRENT TRANSFORMER OUTPUT
Current Transformers
for worldwide cooperation
239
BA THS / BU Transmission Systems and Substations
LEC Support Programme
age of a current transformer, shows the capability of the
transformer to carry burden.
As shown in figure 2, three factors will influence the emf
“E”. It’s
the number of secondary turns
“N”, the core area “A” and the in-
duction in Wb/m
2
“B”. The induction is dependent of the core ma-
terial, which influences the size of the magnetizing current.
For a certain application the secondary turns and the core area
are thus selected to give the required emf output.
3. CURRENT TRANSFORMER OUTPUT
The output required of a current transformer core is dependent of
the application and the type of load connected.
METERING OR INSTRUMENTS Equipment like kW-, kVAr- and A in-
struments or kWh and kVArh meters measures under normal
load conditions. For metering cores a high accuracy for currents
up to the rated current (5-120%), is required. Accuracy classes
for metering cores are 0.1 (laboratory), 0.2, 0.5 and 1.
PROTECTION AND DISTURBANCE RECORDING In Protection relays
and Disturbance recorders the information about a primary dis-
turbance must be transferred to the secondary side. For these
cores a lower accuracy is required but also a high capability to
transform high fault currents and to allow protection relays to
measure and disconnect the fault. Protection classes are 5P and
10P according to IEC 185. Further cores for transient behavior
are defined in IEC 44-6.
In each current transformer a number of cores can be contained.
From three to six cores are normally available and the cores are
then one or two for measuring purposes, and two to four for pro-
tection purposes.