DIFFERENTIAL PROTECTION RELAYS
268
BA THS / BU Transmission Systems and Substations
LEC Support Programme
through fault but the percentage stabilization and an internal sta-
bilization for current transformer saturation means that the re-
quirement can be limited.
Following formula should be used:
E2 ≥ K
TF
x I
smax
(R
ct
+ R
Loop
) where
K
TF
is the transient overdimensioning factor
I
smax
is the max secondary through fault current and
R
Loop
is the max loop resistance seen from connection point.
K
TF
should be selected dependent of the type of Protection relay
supplied and the application.
K
TF
= 2 should be used for RADSB with interposing CT’s.
K
TF
= 3 should be used for RADSB without interposing CT’s or
RET 521 DIfferential protection function.
K
TF
= 4 should be used for SPAD 346 or RET 316.
For one- and a half, Ring busbar or two breaker arrangements
separate stabilizing inputs shall always be used for CT's where
through fault currents can occur.
The modern relays are designed to operate correctly for heavy in-
ternal faults also with saturated CT's so the through fault condi-
tion to ensure that stability is achieved for outer faults will be
dimensioning for the involved cores. It is advisable to use as sim-
ilar saturation level (in current) for the involved current transform-
ers.
Accuracy class 5P according to IEC185, or similar accuracy
class in other standards, should preferable be used.
Pilot wire differential relay RADHL
RADHL operates with a circulating current in the pilot wires. Cur-
rent transformer cores must be provided with the same ratio at
the two terminals but don’t need to be of the same type. The CT
accuracy requirements are based on the most severe external
fault under symmetrical current conditions. Under these condi-
tions and with the CT burden composed of the CT secondary and
lead resistances, plus an allowance of 5 VA for the largest single