PROTECTION AND CONTROL EQUIPMENT
288
BA THS / BU Transmission Systems and Substations
LEC Support Programme
The system includes a supply of marshalling boxes, control pan-
els (and other panels) and internal distribution from different ter-
minals, so that each circuit simply can be opened and checked
for e. g. bad insulation. The terminal numbering system utilized is
described later on.
To enable location of an earth fault, in a operation circuit, at a dis-
connector/earthing switch, with two pole operation, a resistor
shall be connected across the contact at the negative side.
3. PROTECTION AND CONTROL EQUIPMENT
3.1 DESIGN OF PANELS
The panel design and construction shall be done following a
number of general guidelines:
- The layout are to follow the layout of the primary switchgear to avoid con-
fusion.
- The panels should be clearly and visible labelled, so that objects located
in the panel is simply identified.
- The possibilities of future extensions should be kept in mind both in pan-
el design and the location in the room etc.
- Maintenance should be simplified as much as possible and the design
should minimize the risk of mistakes such as testing the wrong object or
the need of making a lot of reconnections, to enable testing.
- Two object per panel, should be avoided but must be done out of cost
reason. The belongings of the object shall then clearly be labelled both
on front and inside the panel.
Terminals
The terminals are small but important components in a substa-
tion. They should have possibility to simple connect and discon-
nect measuring wires with a clearly visible indication.
A maximum of two cores are to be connected at each side of the
terminal and a mixture of single core and stranded wires should
be avoided.
At terminal numbering a clear structure should be used to im-
prove the total quality. The design engineer will by that know