RESONANCE EARTHED SYSTEMS
Earth Fault Protection
for worldwide cooperation
225
BA THS / BU Transmission Systems and Substations
LEC Support Programme
A sensitivity down to below 1A primary is required with reso-
nance earthed systems.
5.3 NEUTRAL POINT VOLTAGES
In order to detect high values of fault resistance, up to 5000 Ω, it’s
often necessary to use a resonance earthing to achieve accept-
able high neutral point voltages (>5V at 5000 Ω). The neutral
point voltage is required to give the directional criteria for the di-
rectional earth fault protection and is also used to provide a
back-up earth fault protection at the busbar or the transformer
bay.
A small neutral point voltage exists, during normal service of the
network, due to unsymmetrical capacitance of the phases to
earth and current leakage at apparatus as surge arresters. Nor-
mally the occurring levels, of unbalance currents, is 0,2 - 5%.
Neutral point detection relays and directional relays should there-
for never be allowed to have sensitivities below 5-10%. Compare
with the requirements of very high sensitivity in solidly earthed
systems.
The neutral point voltages are calculated with the fault resistance
“R
f
”, in series with the neutral reactance “Z
N
”. The neutral imped-
ance consists of the earthing resistance “R
N
”, the capacitive re-
actance of the network “X
C
” and the reactance of the earthing
reactor (normally tuned, “X
L
”).
The factor “R
f
/(R
f
+ Z
N
)” gives the occurring, per unit, voltage.
The “Z
N
” impedance can be calculated “U
n
/( xl
f
)”, where I
f
is
the total fault current.
It must be remembered that “Z
N
”, as well as the vectorial sum
have to be calculated. This means that the capacitive and reac-
tive components “X
C
” and “X
L
” are in opposition and normally will
end up close to zero. This means that the fault current is lower
and the total reactance also will be close to zero.
3