10.2 Analyzing Vapor-Compression Refrigeration Systems 463
Referring again to Fig. 10.5, we can identify another key feature of actual vapor-
compression system performance. This is the effect of irreversibilities during compression,
suggested by the use of a dashed line for the compression process from state 1 to state 2.
The dashed line is drawn to show the increase in specific entropy that would accompany an
adiabatic irreversible compression. Comparing cycle 1–2–3–4–1 with cycle 1–2s–3–4–1, the
refrigeration capacity would be the same for each, but the work input would be greater in
the case of irreversible compression than in the ideal cycle. Accordingly, the coefficient of
performance of cycle 1–2–3–4–1 is less than that of cycle 1–2s–3–4–1. The effect of irre-
versible compression can be accounted for by using the isentropic compressor efficiency,
which for states designated as in Fig. 10.5 is given by
Additional departures from ideality stem from frictional effects that result in pressure drops
as the refrigerant flows through the evaporator, condenser, and piping connecting the vari-
ous components. These pressure drops are not shown on the T–s diagram of Fig. 10.5 and
are ignored in subsequent discussions for simplicity.
Finally, two additional features exhibited by actual vapor-compression systems are shown
in Fig. 10.5. One is the superheated vapor condition at the evaporator exit (state 1), which
differs from the saturated vapor condition shown in Fig. 10.4. Another is the subcooling of
the condenser exit state (state 3), which differs from the saturated liquid condition shown in
Fig. 10.4.
Example 10.3 illustrates the effects of irreversible compression and condenser exit sub-
cooling on the performance of the vapor-compression refrigeration system.
h
c
1W
#
c
m
#
2
s
1W
#
c
m
#
2
h
2s
h
1
h
2
h
1
(c) The coefficient or performance is
Comparing the results of the present example with those of Example 10.1, we see that the power input required by the
compressor is greater in the present case. Furthermore, the refrigeration capacity and coefficient of performance are smaller
in this example than in Example 10.1. This illustrates the considerable influence on performance of irreversible heat transfer
between the refrigerant and the cold and warm regions.
b
Q
#
in
W
#
c
h
1
h
4
h
2s
h
1
241.35 99.56
272.39 241.35
4.57
EXAMPLE 10.3 Actual Vapor-Compression Refrigeration Cycle
Reconsider the vapor-compression refrigeration cycle of Example 10.2, but include in the analysis that the compressor has an
efficiency of 80%. Also, let the temperature of the liquid leaving the condenser be 30C. Determine for the modified cycle
(a) the compressor power, in kW, (b) the refrigeration capacity, in tons, (c) the coefficient of performance, and (d) the rates
of exergy destruction within the compressor and expansion valve, in kW, for T
0
299 K (26C).
SOLUTION
Known: A vapor-compression refrigeration cycle has a compressor efficiency of 80%.
Find: Determine the compressor power, in kW, the refrigeration capacity, in tons, the coefficient of performance, and the
rates of exergy destruction within the compressor and expansion valve, in kW.