360 Electrical Circuit Theory and Technology
Figure 21.9
to field current I
f
until magnetic saturation of the iron circuit of the
generator occurs. Hence the open circuit characteristic is as shown in
Figure 21.9(a).
As the load current on a generator having constant field current
and running at constant speed increases, the value of armature current
increases, hence the armature volt drop, I
a
R
a
increases. The generated
voltage E is larger than the terminal voltage V and the voltage equation
for the armature circuit is V D E I
a
R
a
. Since E is constant, V decreases
with increasing load. The load characteristic is as shown in Figure 21.9(b).
In practice, the fall in voltage is about 10% between no-load and full-load
for many d.c. shunt-wound generators.
The shunt-wound generator is the type most used in practice, but the
load current must be limited to a value that is well below the maximum
value. This then avoids excessive variation of the terminal voltage. Typical
applications are with battery charging and motor car generators.
(c) Series-wound generator
In the series-wound generator the field winding is connected in series
with the armature as shown in Figure 21.10.
Figure 21.10
Characteristic
The load characteristic is the terminal voltage/current characteristic. The
generated e.m.f. E, is proportional to ω and at constant speed ω (D
2n) is a constant. Thus E is proportional to . For values of current
below magnetic saturation of the yoke, poles, air gaps and armature core,
the flux is proportional to the current, hence E / I. For values of
current above those required for magnetic saturation, the generated e.m.f.
is approximately constant. The values of field resistance and armature
resistance in a series wound machine are small, hence the terminal voltage
V is very nearly equal to E. A typical load characteristic for a series
generator is shown in Figure 21.11.
In a series-wound generator, the field winding is in series with the
armature and it is not possible to have a value of field current when the
terminals are open circuited, thus it is not possible to obtain an open-
circuit characteristic.
Series-wound generators are rarely used in practise, but can be used as
a ‘booster’ on d.c. transmission lines.
(d) Compound-wound generator
In the compound-wound generator two methods of connection are used,
both having a mixture of shunt and series windings, designed to combine
the advantages of each. Figure 21.12(a) shows what is termed a long-
shunt compound generator, and Figure 21.12(b) shows a short-shunt
Figure 21.11