
62 API RECOMMENDED PRACTICE 14FZ
7.2.4 Motor Enclosures
7.2.4.1 Motor enclosures should be selected both to pro-
vide optimum protection from the environment and also to
satisfy the area classification requirements.
7.2.4.2 In Class I, Zone 0 locations, it is recommended that
installation of motors and related electrical apparatus be
avoided. When installed in Zone 0 locations motors shall be of
the submersible type and immersed in liquid during operation.
Submerged pump motors should be provided with low liquid
level protection and either motor undercurrent protection or
pump discharge pressure sensors to activate if the pump loses
suction. These sensors should automatically shut down power
to the motor and activate audible and visual alarms.
7.2.4.3 In Class I, Zone 1 locations, motors shall be
approved to meet one of the following specific methods of
construction: Flameproof (protection type “d”), Increased
Safety (protection type “e”), pressurized (protection type
“p”), or a special submerged unit as referenced in 7.2.4.2.
Alternatively, motors in Class I, Zone 1 locations may either
be explosionproof and listed for use in a Class I, Division 1
location, or employ one of the protection techniques listed in
NEC Article 501-8(a) 2, 3, or 4 for Class 1, Division 1 loca-
tions.
7.2.4.4 In Class I, Zone 2 locations, motors having type of
protection “n” approved for the locations in which they are
used, or totally enclosed, open drip-proof, or NEMA weather
protected Type I or Type II motors that have no arcing or
high-temperature devices may be used. Note that most sin-
gle-phase motors have a centrifugal switch, which is an arc-
ing device. Arcing or high-temperature devices shall be
approved for use in Class I, Zone 2 hazardous locations or
provided with suitable enclosures. Totally-enclosed motors
generally are preferred to open motors because the insulation
of totally enclosed motors is not continuously exposed to the
salt-laden air. For improved resistance to corrosion, “chemi-
cal type” motors are recommended in preference to standard
motors for integral horsepower motors in the NEMA frame
sizes. These totally enclosed motors normally are available
with all cast metal parts, noncorrosive and nonsparking cool-
ing fans, corrosion-resistant hardware, stainless steel name-
plates, and paint coatings on both the interior and exterior
parts. In larger sizes, totally enclosed fan-cooled (TEFC),
totally enclosed water-air-cooled (TEWAC), or totally
enclosed air-to-air cooled (TEAAC) motors with sealed insu-
lation systems are recommended.
7.2.5 Bearings
7.2.5.1 Horizontal Motors
Anti-friction-type, grease-lubricated bearings are recom-
mended for horizontal motors in the NEMA frame sizes and
should be evaluated for motors as large as 250 hp (500 hp at
1200 RPM and less). Oil-lubricated sleeve bearings frequently
are used for larger horizontal motors. Grease-lubricated anti-
friction bearings should be designed with seals or shields to
permit long periods of operation without re-greasing; how-
ever, it is recommended that motors be equipped with grease
fill and drain holes to permit re-greasing in the field.
7.2.5.2 Vertical Motors
Thrust bearings in vertical motors normally are of the ball
or roller type. Grease lubrication is generally acceptable for
“normal thrust” motors; however, oil lubrication is recom-
mended for “high thrust” motors in the larger sizes. The up-
and-down thrust requirements should be defined when motors
are expected to carry thrust loads from driven equipment.
7.2.6 Temperature Considerations
Electric motors normally are designed to operate at their
nameplate rating in ambient temperatures up to 40°C. Where
motors are expected to be operated continuously in higher
ambient temperatures, consideration should be given to derat-
ing the motor or using a motor specially designed for the
higher temperature. Special attention should be given to the
selection of the bearing lubricants if the motor is to operate in
unusually high or low temperatures. See also 6.7.11.
7.2.7 Torque Characteristics
Motor torque characteristics should be selected both to
match load requirements and also to consider limitations in
generating capacity. Normal-starting torque (NEMA design
B) motors should be suitable for low-starting torque loads
(such as centrifugal pumps and fans). High-starting torque
(NEMA design C) motors may be needed for loads requiring
high-starting torque (such as positive displacement pumps
and compressors).
7.2.8 Insulation
Most standard NEMA frame motors are fabricated using
nonhygroscopic NEMA Class F or H insulation. In totally
enclosed motors, the normal insulation can be expected to
provide satisfactory service. If open drip-proof or weather-
protected motors are selected, it is recommended that the
insulation be a sealed system. Motors with NEMA Class F
insulation and with a NEMA Class B rise at rated motor
horsepower are available in most motor sizes and types and
are recommended to provide an increased service factor and
longer insulation life.
7.2.9 Locked Rotor kVA
Three-phase induction motors normally are designed for a
starting kVA of 5-6 times the horsepower rating. This starting
kVA corresponds to NEMA locked rotor Codes F and G and