
56 API RECOMMENDED PRACTICE 14FZ
6.10.2.5 The facility structure or hull of a floating facility
should not serve as a current-carrying conductor except for
the following systems:
a. Cathodic protection systems.
b. Limited and locally grounded systems, such as battery
systems for engine starting and control that have a one-wire
system and have the ground lead connected to the engine.
c. Insulation level monitoring devices with circulating cur-
rents not exceeding 30 mA.
d. Welding systems with a structure or hull return.
Note: When welding on facilities with the welding machine located
on an adjacent vessel or barge, the facilities should be effectively
bonded to the vessel or barge to avoid galvanic corrosion of the facil-
ity or the vessel.
e. Ground-fault detection systems.
6.10.3 Equipment Grounding
6.10.3.1 Grounding of electrical equipment on fixed and
floating offshore petroleum facilities in a positive manner is
of particular importance because personnel standing on steel
decks or in contact with steel framing present a low imped-
ance path to ground, effectively grounded. In addition, the
dampness and salt spray contribute to the breakdown of insu-
lation and to the possibility of leakage on the surface of insu-
lators and similar devices. On platforms with wooden or con-
crete decks, equipment-grounding conductors should be
installed between electrical equipment and a grounding net-
work. It is recommended that all metal equipment, such as
buildings, skids, and vessels be grounded to the steel structure
or grounding network. Exposed, noncurrent-carrying metal
parts of fixed equipment that may become energized because
of any condition shall be grounded. Equipment that is welded
to the structure or deck is considered to be adequately
grounded. The physical contact obtained when equipment is
bolted to a steel structure is not necessarily an adequate effec-
tive ground because of paint and possible corrosion. Exposed,
noncurrent-carrying metal parts of portable electrical equip-
ment shall be grounded through a conductor in the supply
cable to the grounding pole in the receptacle.
6.10.3.2 For sizing equipment grounding conductors, refer
to NEC Table 250-122.
6.10.3.3 Each individual grounding conductor should be
bare, or, if insulated, have a continuous outer finish that is
either green or green with one or more yellow stripes. Alter-
natively, the grounding conductor can be identified with a
green marking or other equally effective means at each termi-
nation and accessible box opening throughout the system.
Conductors with green insulation or markings shall not be
used for any purpose other than grounding.
6.10.3.4 To provide the desired safety, equipment ground-
ing should accomplish the following:
a. Grounding should limit the voltage (normally to 42 V
maximum) that may be present between the equipment in
question and any other grounded object with which personnel
may be in contact at the same time.
b. For solidly grounded systems, grounding should present a
low impedance path for short circuit current to return to the
source of power, thus opening a fuse or tripping a circuit
breaker. This requires that the equipment ground be bonded
to the system ground.
6.10.4 Ground Fault Indication
6.10.4.1 A ground fault indication system should be
installed on each separately-derived AC electrical power dis-
tribution system (e.g., generators and transformers) that is not
solidly or low impedance grounded. This system should be
designed to provide an indication of a ground fault condition,
with the ground fault indicators provided at a location(s) that
is commonly accessed by operating personnel. Separate,
ground-fault indication systems are not required when ground
fault protection systems are provided.
6.10.4.2 All armor or other metal coverings of cable shall
be electrically continuous throughout the entire length and
shall be effectively grounded. It is recommended that metal
coverings be grounded at all terminations.
6.11 ELECTRICAL ENCLOSURES
6.11.1 General
Electrical conductors, buses, terminals, or components that
present a shock hazard are not permitted to be uninsulated if
exposed.
6.11.1.1 Electrical equipment enclosures are provided for
both personnel and equipment protection. For offshore use, it
is recommended that enclosures be constructed of corrosion-
resistant materials, such as copper-free aluminum, stainless
steel (Type 316 usually preferred because Type 303 and 304
are more subject to pitting-type corrosion), suitable plastic,
fiberglass, or hot-dipped galvanized steel. Enclosure hard-
ware constructed of Type 316 stainless steel is recommended.
6.11.1.2 Refer to Table 6-10 for a listing and description of
various NEMA enclosures available. For additional informa-
tion, see NEMA ICS6 and NEMA 250. Refer to Table 6-11
for a listing and description of various IEC enclosures avail-
able. For additional information, see IEC 529. Refer to
NEMA MG 1 for additional information concerning enclo-
sures for rotating apparatus.
6.11.1.3 Space heaters, breathers, or drains, or a combina-
tion of such, should be considered for all enclosures as a