
DESIGN AND INSTALLATION OF ELECTRICAL SYSTEMS FOR FIXED AND FLOATING OFFSHORE PETROLEUM FACILITIES
FOR UNCLASSIFIED AND CLASS I, ZONE 0, ZONE 1, AND ZONE 2 LOCATIONS
43
6.8.2 Seal Requirements
6.8.2.1 Enclosure Entries
6.8.2.1.1 In Zone 1 and Zone 2 locations, a seal shall be
installed in every conduit or cable directly entering an enclo-
sure containing an arcing or high-temperature device where
the enclosure is required to be flameproof or explosionproof.
6.8.2.1.2 Cables installed in Zone 1 locations require a seal
at all terminations required to be direct entry flameproof or
explosionproof.
6.8.2.1.3 Multi-conductor Type MC-HL cables should be
sealed with an approved fitting after removal of the overall
jacket and any other covering so the sealing compound will
surround each individual insulated conductor in such a man-
ner as to minimize the passage of gases and vapors. An excep-
tion to this requirement is that cables containing shielded
cables and twisted pair cables do not require the removal of
the shielding material or separation of the twisted pairs pro-
vided the termination is made with an approved means to min-
imize the entrance of gases and vapors and to prevent
propagation of flame into the cable core. The conventional
sealing type cable terminator approved to comply with UL
2225 does not inherently meet the criteria for this exception.
6.8.2.1.4 Where cables with a gas/vaportight continuous
sheath capable of transmitting gases or vapors through the
cable core are installed within conduit, the annulus space
between the conduit and the cable(s) should be sealed with
sealing compound, and the cable core should be sealed after
removing the jacket and any other coverings so that the seal-
ing compound will surround each individual conductor and
the outer jacket. An exception for multiconductor cables,
shielded cables, and twisted pair cables with a gas/vaportight
continuous sheath capable of transmitting gases or vapors
through the cable core, is that such cables can be considered
as a single conductor by sealing the cable in the conduit
within 18 in. (457 mm) of the enclosure, but it is also neces-
sary to seal the cable end within the enclosure by an approved
means to minimize the entrance of gases or vapors and to pre-
vent the propagation of flame into the cable core.
6.8.2.1.5 The conduit system between an enclosure and a
required seal shall be flameproof or explosionproof, even in
Zone 2 locations, as the conduit system must be able to with-
stand the same internal explosive pressure as the enclosure to
which it is attached. In Zone 1 and Zone 2 locations,
approved explosionproof unions, reducers, couplings,
elbows, capped elbows, and conduit bodies similar to “L”,
“T”, or “Cross” type are the only enclosures or fittings
allowed between the sealing fitting and the enclosure. The
conduit bodies cannot be larger than the largest trade size of
the interconnecting conduit/nipples.
In Zone 1 locations only, seals shall be installed in each 2
in. size or larger conduit run entering an enclosure that con-
tains splices, taps, or terminals. All seals should be installed
as close as practicable, but in no case more than 18 in. from
the enclosures to which they are attached.
6.8.2.2 Process Instruments
As required by the NEC 501-5 (f)(3), conduit seals or barri-
ers and drains shall be installed in each conduit or cable con-
nection to devices installed on process lines or process vessels
containing flammable fluids and that depend on a single-seal
diaphragm or tube (such as a Bourdon tube or a thermowell) as
a barrier between the process fluid and the conduit or cable.
This is to prevent flammable process fluids from entering con-
duit or cable systems and being transmitted to unclassified
locations or to electrical arcing or high temperature devices in
other portions of the system if the primary seal fails.
a. Draining provisions should be such that process fluid leaks
past the primary seal will be obvious. Conventional conduit
drains and drain seals may not be capable of relieving process
leaks at a rate sufficient to adequately relieve the pressure
generated by primary seal failure to 6 in. of water column
(1493 Pascals).
b. As an alternate secondary sealing method, an approved
assembly consisting of a minimum of 4 feet of Type MI cable
and terminations can be installed between the cable or con-
duit system and single barrier process instruments or devices.
c. The additional seal or barrier and the interconnecting
enclosure or conduit system should meet the temperature and
pressure conditions to which they will be subjected upon fail-
ure of the primary seal. Ordinary conduit seals typically
cannot meet these criteria because of their permissible leakage
rate. Typical examples of such devices are solenoid valves and
level, pressure, temperature and flow switches or transmitters.
This requirement applies even in unclassified locations.
6.8.2.3 Classified Area Boundaries
6.8.2.3.1 Wherever a conduit run passes from a Zone 0
location to a Zone 1 location, from a Zone 1 location to a
Zone 2 location, from a Zone 2 location to an unclassified
location, or any combination thereof, a seal shall be placed in
the conduit run at the boundary, on either side. Except for
approved explosionproof reducers at the conduit seal, the
conduit system shall not contain any union, coupling, box, or
other fitting between the sealing fitting and the point at which
the conduit leaves the Zone 1 or Zone 2 location. An excep-
tion to the above is that unbroken rigid metal conduit that
passes completely through a Zone 1 or a Zone 2 location is
not required to be sealed at the classification boundary if the
termination points of the unbroken conduit are in unclassified
locations and the conduit has no fitting less than 12 in.
beyond each boundary.