
38 API RECOMMENDED PRACTICE 14FZ
densation or where humidity control is provided. A continuous cor-
rugated aluminum armor or sheath is preferred over an interlocked
armor or sheath.
Note 2: Good engineering judgment should be used in applications
utilizing cables listed in 6.4.2.4. For example, it may be necessary to
provide additional mechanical protection for certain cables.
6.4.3 Instrumentation, Control, and Communication
Systems Wiring
6.4.3.1 Wiring methods as described in 6.4.2.2 and 6.4.2.3
for Zone 1 locations and 6.4.2.4 and 6.4.2.5 for Zone 2 loca-
tions can be used for remote-control, signal-ing, and commu-
nications circuits.
6.4.3.2 In Zone 2 locations, ITC and PLTC cables can be
used. In addition, application-specific cables that satisfy the
mechanical sheath requirements for type MC or TC cables
and meet the flame propagation requirements of IEEE 1202
may be used.
6.4.3.3 Intrinsically safe system wiring in Zone 0, Zone 1
or Zone 2 locations (see 4.3.3) may utilize any method
acceptable for wiring in unclassified locations provided that
the wiring method is suitable for the environment (for exam-
ple, oil and sunlight resistance may be required depending
upon the installation location); meets the requirements of the
IEEE Std 1202 flammability test, CSA FT-4 flammability
test, IEEE Std 383 flammability test, or the Cable Tray Flame
Test described in UL 1581; and is installed in accordance
with NEC Article 504. The IEEE Std 1202 or CSA FT-4 test
is preferred. In addition, some installation situations may
require sealing (gas blocking type seal) of cable and cable
cores at area classification boundaries to minimize the pas-
sage of gases or process fluids from one Zone to another, or to
a non-hazardous area.
6.4.4 Sheath Grounding
When utilizing TC or shipboard cables, which do not inher-
ently provide a grounding means, the equipment grounding
path should be carefully considered. The armor of shipboard
cable should be grounded, but cannot be used as the grounding
conductor. Thus, an appropriately sized grounding conductor
should be included within each cable, or other adequate
grounding means provided to comply with NEC Article 250. In
unclassified and Zone 2 locations, when the metallic sheath is
approved as a grounding conductor, the continu-ous corrugated
metallic sheath of type MC cable or the combined metallic
sheath and grounding conductors may be used as the ground-
ing conductor when used with termination fittings that are
NRTL-listed to meet UL 514B and UL 467.
6.4.5 Flexible Cords
Flexible cords designated for extra-hard usage by NEC
Table 400-4 may be used in Zone 1 or Zone 2 locations in
accordance with NEC Article 501-11, but are recommended
only for temporary service in Zone 1 locations.
6.4.6 Heat Trace Cables
For Heat Trace Systems, refer to 11.6.
6.4.7 Special Considerations for Wiring Methods
in Classified Locations
6.4.7.1 Careful consideration should always be given to the
routing of cable trays and cables to avoid mechanical damage.
TC, non-armored PLTC, ITC, MV, shipboard cables, and
other similar non-armored cables are not as mechanically rug-
ged as armored cables. These non-armored cables should be
installed within a continuous cable support system or cable
tray to provide protection against mechanical damage. When-
ever the cables leave the support system or cable tray, they
should be mechanically protected by installing them in con-
duit, angles, channels, or raceways or by other suitable means.
6.4.7.2 All cables, except flexible cords, not installed in a
metal raceway such as rigid or flexible metal conduit should
meet the requirements of the IEEE Std 1202 flammability
test, CSA FT-4 flammability test, IEEE Std 383 flammability
test, or the Cable Tray Flame Test described in UL 1581. The
IEEE Std 1202 or CSA FT-4 test is preferred. Listed Marine
Shipboard Cables, Type MC-HL cables, and cables suitable
for use in cable trays in accordance with the NEC (e.g., TC,
ITC or PLTC) meet at least one of the above requirements.
Other cables, except flexible cords, should have the designa-
tion “Cable Tray Use” or “CT Use” marked on or in the
cable. Flexible cords should meet the requirements of UL
1581 VW-1 or CSA FT-1 as a minimum.
6.4.7.3 Where movement or vibration requires a flexible
connection, the following systems are recommended:
6.4.7.3.1 In Zone 1 locations, flameproof or explosion-
proof flexible metal conduit fittings, or armored and sheathed
marine shipboard cable with flexible stranded conductors. For
portable equipment, a flexible cord designated for extra-hard
usage by NEC Table 400-4 and containing an equipment
grounding conductor; reference NEC 501-11.
6.4.7.3.2 For fixed equipment in Zone 2 locations, liquid-
tight flexible metallic conduit (6 ft maximum) with an exter-
nal or internal bonding jumper; or, flexible cord approved for
extra-hard usage and containing an equipment grounding
conductor. Where practical, the length of flexible connections
should not exceed three feet. For portable equipment, flexible
cord approved for extra-hard usage and containing an equip-
ment grounding conductor; reference NEC 501-11.