
104 API RECOMMENDED PRACTICE 14FZ
4/5C2.15.5 Power Output of Gas Turbines
To satisfy the requirements of 4/5A2.1. the required power
output of gas turbine prime movers for ship’s service genera-
tor sets is to be based on the maximum expected inlet air tem-
perature.
4/5C2.17 DIESEL ENGINES FOR GENERATORS
Diesel-engine prime movers are to meet the applicable
requirements in Section 4/4 and in addition are to comply
with the following requirements.
4/5C2.17.1 Operating Governor
An effective operating governor is to be fitted on prime
movers driving main or emergency electric generators and is
to be capable of automatically maintaining the speed within
the following limits. Special consideration will be given when
an installation requires different characteristics.
a. Momentary Speed Variations (1998). The momentary
speed variations, when running at the following loads, is to be
within 10% of the rated speed when:
1. (1998) the full load (equal to rated output) of the gener-
ator is suddenly thrown off, and
2. 50% of the full load of the generator is suddenly
thrown on followed by the remaining 50% load after an
interval sufficient to restore the speed to steady state.
3. The speed is to return to within 1% of the final steady
state speed in no more than 5 seconds.
4. (1998) The application of electrical load in more than
two steps can be used where the system design provides
for incremental grouping of loads with due consideration
for automatically switched loads, critical recovery loads
following a blackout, and emergency transfer of loads
from a troubled generator set to the surviving sets operat-
ing in parallel (see Figure 4/5C.1). The details of load
management system are to be described fully in the design
documentation and its satisfactory operation is to be dem-
onstrated to the Surveyor during the vessel’s trial. In this
case, due consideration is to be given to the power
required for the electrical equipment to be automatically
switched on after black-out and to the sequence in which
it is connected. This applies analogously also for genera-
tors to be operated in parallel and where the power has to
be transferred from one generator to another in the event
that any one generator has to be switched off.
b. Speed Variations in Steady State (1998). The steady state
speed variation is to be within 5% of the rated speed at all
loads between no load and full load.
c. Emergency Generator Prime Movers (1998). Prime mov-
ers driving emergency generators are to be able to maintain
the speed within the limits in 4/5C2.17.1a and lb when the
full load of the emergency generator is suddenly thrown on.
Where loads are applied in multiple steps, the first applied
load is not to be less than the required emergency load (see 4/
5A3.3.1) or 4/5C2.17.1a4 whichever is the greater. Where
loads are applied in multiple steps, the first applied load is not
to be less than the sum of all emergency loads that are auto-
matically connected.
4/5C2.17.2 Overspeed Governor
In addition to the normal operating governor each auxiliary
diesel engine having a maximum continuous output of 220
kW and over is to be fitted with a separate overspeed device
so adjusted that the speed cannot exceed the maximum rated
speed by more than 15%. Provision is to be made for hand
tripping. See 4/5C2.13 for pressure-lubricated machines.
4/5C2.19 ALTERNATING-CURRENT (AC)
GENERATORS (1997)
4/5C2.19.1 Control and Excitation of Generators
Excitation current for generators is to be provided by
attached rotating exciters or by static exciters deriving their
source of power from the machine being excited.
4/5C2.19.2 Voltage Regulation
a. Voltage Regulators. A separate regulator is to be supplied
for each AC generator. When it is intended that two or more
generators will be operated in parallel, reactive-droop com-
pensating means are to be provided to divide the reactive
power properly between the generators.
b. Steady Conditions. Each AC generator for ship’s service
driven by its prime mover having governor characteristics
complying with 4/5C2.15.1 or 4/5C2.17.1 is to be provided
with an excitation system capable of maintaining the voltage
under steady conditions within plus or minus 2.5% of the
rated voltage for all loads between zero and rated load at rated
power factor. These limits may be increased to plus or minus
3.5% for emergency sets.
c. Short Circuit Conditions. Under steady-state short circuit
conditions, the generator together with its excitation system is
to be capable of maintaining a current of not less than 3 times
its rated full load current for a period of 2 seconds or of such
magnitude and duration as required to properly actuate the
associated electrical protective devices.
4/5C2.19.3 Parallel Operation
For AC generating sets operating in parallel, the following
requirements are to be complied with. See also 4/5A.5.5.2 for
protection of AC generators in parallel operation.
a. Reactive Load Sharing. The reactive loads of the individ-ual
generating sets are not to differ from their proportionate share
of the combined reactive load by more than 10% of the rated