Chapter 25 Substation Control and Automation
25-5
and it must be ensured that the computer hardware and
communications links have sufficient performance to ensure
prompt processing of incoming data. Overload in this area can
lead to one or more of the following:
x undue delay in updating the system status
diagrams/events log/alarm log in response to an
incident
x corrupti
on of system database, so that the information
presented to the operator is not an accurate
representation of the state of the actual electrical
system
x system lockup
As I/O at the bay level, both digital and analogue will typically
be handled by intelligent relays or specialised IEDs, it is
therefore important to ensure that these d
evices have sufficient
I/O capacity. If additional IEDs have to be provided solely for
ensuring adequate I/O capacity, cost and space requirements
will increase. There will also be an increase in the number of
communications links required.
25.4 SUBSTATION AUTOMATION
FUNCTIONALITY
The hardware implementation provides the physical means to
implement the functionality of the substation automation
scheme. The software provided in the various devices is used
to implement the functionality required. The software may be
quite simple or extremely complex – Table 25.1 illustrates the
functionality that may be provided in a large scheme.
The description of the electrical network and the characteristics
of the various devices associated with the network are held
within the computer as a database or set of databases. Within
each database, data is organised into tables, usually on a ‘per
device’ basis that reflects the important characteristics of the
device and its interrelationship with other devices on the
network. Electrical system configuration changes require
modification of the database using an appropriate software
tool. The tool is normally a high level, user-friendly interface,
so that modifications to the one-line can be drawn directly on-
screen, with ‘pick-and–place’ facilities. This work would
normally be done offline on the Engineers’ workstation, if
available, or as a background task on the control computer if
not. Careful and extensive checking of the data is required,
both before and after entry into the database, to ensure that no
errors have been made. Full testing on the new configuration
using a simulator is recommended prior to use of the new
database on the main control computer to ensure that there is
minimal possibility of errors.
The software is written as a set of well-proven, standard
modules, so there is little or no need for new modules to be
written and tested for a particular substation. The required
data for the calculations performed by the software is held in
the network database. This means that adding functionality
later is not difficult, so long as the database design has
considered this possibility. There may be problems if the
electrical system configuration is altered or additional
functionality added, in reading historical data prior to the
change. Training of operations personnel will inevitably be
required in operation of the system, configuration
management and automation system maintenance.
Automation system suppliers will be able to provide
configuration management and system maintenance services
under contract if required, often with defined cost schedules
and response times so financial management of the
automation scheme once installed is well-defined.
The issuing of commands to switching devices in the system
has to be carefully structured, in order to prevent commands
that would cause a hazard being issued. A hierarchical
structure is commonly used as shown in Figure 25.6,
beginning with the requirement for an operator wishing to
issue a command to switching devices to log-in to the system
using a password, or other means of authentication.
Interlocking CB's Isolators Contactors
Tripping sequences CB failure Intertripping Simultaneous trips
Switching sequences Automatic transformer changeover Automatic busbar changeover Restoration of supply following faul
Network re-configuration
Load managemen
Load shedding Load restoration Generator despatch
Transformer supervision OLTC control Load managemen
Energy monitoring Import/export control Energy managemen
Power factor control
Switchgear monitoring AIS monitoring GIS monitoring
Equipment status Relay status CB status Isolator status
Parameter setting Relays Transformers Switching sequences IED configuration
HMI functionality
Access control One-line views System views Event logging
HMI functionality
Trend curves Harmonic analysis Remote access Disturbance analysis
HMI functionality
Interface to SCADA Alarm processing
Table 2
.
: Typical substation automation functionalit
© 2011 Alstom Grid. Single copies of this document may be filed or printed for personal non-commercial use and must include this
copyright notice but may not be copied or displayed for commercial purposes without the prior written permission of Alstom Grid.