Network Protection & Automation Guide
C-2
C.3 AC VOLTAGE DIPS & SHORT
INTERRUPTIONS
Standard Typical Details
AC voltage interruptions, EN 61000-4-
11:2004 and EN60255-11 : 2008
10ms, 20ms with no loss of protection.
50ms, 100ms, 200ms, 500ms, 5s with temporary loss of
protection.
AC voltage dip, EN 61000-4-11:2004
and EN60255-11 : 2008
60% @ 200ms, 30% @ 500ms, 20% @ 5s with no loss of
protection.
C.4 HIGH FREQUENCY DISTURBANCE TESTS
Standard Typical Details
1MHz burst Immunity test, EN
60255-22-1:2008 Class III
2.5kV common mode between independent circuits and
between independent circuits and case earth.
1kV differential mode across terminals of the same circuit
(except metallic contacts).
C.5 FAST TRANSIENT
Standard Typical Details
Fast Transient, EN 61000-4-4:2004
Level 4
4kV 5kHz, power supply and earth ports.
2kV 5kHz, all other circuits (excluding power supply and earth
ports).
Fast Transient, EN 60255-22-4:2008
Class A.
4kV 5kHz and 100kHz, applied to all circuits excluding
communication ports.
2kV 5kHz and 100kHz, applied to communication ports.
C.6 CONDUCTED EMISSIONS
Standard Typical Details
Power supply, EN55022: 2006 and
EN60255-25: 2000
0.15 - 0.5MHz, 79dB
P
V (quasi peak) 66dB
P
V (average).
0.5 - 30MHz, 73dB
P
V (quasi peak) 60dB
P
V (average).
Permanently connected
communications ports, EN55022:
2006 and EN60255-25: 2000
0.15 - 0.5MHz, 97dB
P
V (quasi peak) 84dB
P
V (average).
0.5 - 30MHz, 87dB
P
V (quasi peak) 74dB
P
V (average).
C.7 RADIATED EMISSIONS
Standard Typical Details
Radiated emissions, EN55022:2006
(EN60255-25:2000)
30 - 230MHz, 40dB
P
V/m at 10m measurement distance.
230 - 1000MHz, 47dB
P
V/m at 10m measurement distance.
C.8 CONDUCTED IMMUNITY
Standard Typical Details
Conducted immunity, EN 61000-4-6:
2009 Level 3 (EN60255-22-6: 2001)
10V emf @ 1kHz 80% am, 150kHz to 80MHz.
Spot tests at 27MHz, 68MHz.
C.9 RADIATED IMMUNITY
Standard Typical Details
Radiated immunity, EN 61000-4-3:
2006 Level 3
10 V/m 80MHz - 1GHz @ 1kHz 80% am.
Radiated immunity from digital radio
telephones, EN 61000-4-3: 2006
Level 4
30 V/m 800MHz – 960MHz and 1.4GHz – 2GHz @ 1kHz
80% am.
Radiated immunity, EN 60255-22-3:
2007 Class III)
10 V/m 80MHz - 1GHz and 1.4GHz – 2.7GHz @ 1kHz 80%
am.
Spot tests at 80MHz, 160MHz, 380MHz, 450MHz,
900MHz, 1850MHz and 2150MHz.
C.10 ANSI/IEEE RADIATED IMMUNITY
Standard Typical Details
ANSI Radiated Immunity/IEEE
C37.90.2 2004
35 V/m 80MHz - 1GHz, @ 1kHz 80% am.
35 V/m 80MHz - 1GHz, 100% pulse modulated.
Spot tests at 80MHz, 160MHz, 450MHz, 900MHz and
900MHz (200Hz rep. freq., pulse modulated).
C.11 ELECTROSTATIC DISCHARGE
Feature Details
ESD, EN61000-4-2:2009 Level 3 and
Level 4 (EN60255-22-2: 2008)
Level 4: 15kV air discharge. Tests carried out both with and
without cover fitted.
Level 4: 8kV contact discharge. Tests carried out both with
and without cover fitted.
Level 4: 15kV indirect discharge. Tests carried out both with
and without cover fitted.
C.12 IEC SURGE IMMUNITY
Feature Details
Power supply, EN61000-4-5:2006
Level 4 (EN60255-22-5:2002)
4kV common mode 12
:
source impedance, 2kV differential
mode 2
:
source impedance, level 4.
CT and VT inputs, opto inputs, output
relays, EN61000-4-5:2006 Level 4
(EN60255-22-5:2002)
4kV common mode 42
:
source impedance, 2kV differential
mode 42
:
source impedance, Level 4.
Cable screen, EN61000-4-5:2006
Level 4 (EN60255-22-5:2002)
4kV common mode 2
:
source impedance
C.13 POWER FREQUENCY MAGNETIC FIELD
IMMUNITY
Standard Typical Details
Power Frequency Magnetic Field
Immunity, EN61000-4-
8:1993+A1:2001 Level 5.
100A/m field applied continuously in all planes for the EUT in
a quiescent and tripping state (EUT – ‘Equipment Under
Test’).
1000A/m field applied for 3s in all planes for the EUT in a
quiescent and tripping state.