
170 SECTION 3 Motors
TR
CONTROL TRANSFORMER
S
TR
S
2C
TR
THERMOSTAT
1C
2C
OL
A basic control schematic for a wye-delta starter
is shown in Figure 15–22. To understand the opera-
tion of this circuit assume that timer TR has been set
for a delay of 3 seconds.
• When the thermostat contact closes, a current path
exists through coils 1C, TR, and S, Figure 15–23.
• The 1C load contacts close to supply power to the
motor T leads.
• The S contacts change position also. The two S
load contacts close and connect the stator wind-
ing in a wye con guration by shorting T4, T5,
and T6 together. The normally open S contact
connected in series with coil 2C opens to provide
interlocking protection.
• After a delay of 3 seconds, both TR contacts
change position, Figure 15–24.
• The normally closed TR contact connected in
series with S coil opens and deenergizes S contactor
causing all S contacts to return to their normal
position. The normally closed S contact connected
in series with coil 2C recloses to provide a current
path to coil 2C.
• When the normally open TR contact connected
in series with coil 2C closes, coil 2C energizes
causing all 2C contacts to change position. The
2C load contacts close and reconnect the motor
stator windings in a delta con guration. The nor-
mally closed 2C contact connected in series with
S coil opens to provide interlocking protection.
Part Winding Starters
Another method for reducing the starting current
of large three-phase squirrel-cage motors is part
winding starting. Motors intended for use with
part winding starting contains two separate stator
windings, Figure 15–25. Each winding is rated for
Figure 15–22
Basic control schematic for wye-delta starting. (Source: Delmar/Cengage Learning)