
124 SECTION 3 Motors
lead of the run and start windings connected as
shown in Figure 11–15. To test the windings for
an open, connect one ohmmeter lead to the com-
mon motor terminal, and the other meter lead to
the run winding. The ohmmeter should indicate
continuity through the winding. The resistance of
the run winding of a single-phase motor can vary
greatly from one motor to another. The winding
resistance of a single-speed motor may be only one
or two ohms, while the resistance of a multi-speed
fan motor may be 10 to 15 ohms.
To test the start winding for an open, connect the
ohmmeter leads to the common terminal and the
S terminal. The start winding should indicate conti-
nuity, and should have a higher resistance than the
run winding. This difference of resistance may not
be great, but the start winding should have a higher
resistance than the run winding.
To test the stator winding for a ground, connect
one of the ohmmeter leads to the case of the motor,
Figure 11–16. Alternately check each motor termi-
nal with the other ohmmeter lead. The ohmmeter
should indicate no continuity between either wind-
ing and the case of the motor.
A shorted start winding can sometimes be
detected by the fact that the motor will not start, but
will run if the shaft is turned by hand. The motor
will produce a humming sound but will not turn
when power is rst applied to it. The shaft can be
turned in either direction by hand and the motor
will continue to run in that direction.
C
SR
C
SR
Figure 11–15
Testing the split-phase motor for an open winding.
(Source: Delmar/Cengage Learning)
Figure 11–16
Testing a split-phase motor for a grounded winding.
(Source: Delmar/Cengage Learning)
REVERSING DIRECTION
OF ROTATION
The direction of rotation of a split-phase motor can
be reversed by changing the start winding leads or
the run winding leads, but not both. The rotation is
generally reversed by changing the start winding
leads with respect to the run winding. Some motor
manufacturers bring both start winding leads to the
outside of the motor. This permits the service techni-
cian to decide the direction of rotation the motor is
to turn when it is installed on the unit.
DUAL-VOLTAGE MOTORS
Single-phase motors can also be constructed to
operate on two separate voltages. These motors
are designed to be connected to 120 or 240 volts.
A common connection for this type of motor con-
tains two run windings and one start winding,
Figure 11–17. The run windings are labeled T1–T2,
and T3–T4. The start winding is labeled T5 and T6.
In the circuit shown in Figure 11–17, the windings
have been connected for operation on a 240-volt
line. Each winding is rated at 120 volts. The two
run windings are connected in series, which causes
each to have a voltage drop of 120 volts when con-
nected to 240 volts. Notice that the start winding
has been connected in parallel with one of the run
windings. This causes the start winding to have an