Heating
Load
Calculations
Structure
heat load
is
composed
of (1)
transmission
loss through walls, windows,
and
roof
and (2)
infiltra-
tion
of
cold outside air, which must
be
heated
to the
design space temperature.
The
transmission loss through
any
portion
of the
structure
envelope
is
H
= U x A x
A7
(23-4)
where,
in SI
units,
H is the
heat loss
in
watts
per
hour,
U
is the
overall heat transmission coefficient
in W/
(m
2
• h •
0
C),
A is the
surface area
in
square meters,
and
AT
is the
inside-to-outside temperature difference
in
degrees Celsius.
In
U.S. customary units,
H is in
Brit-
ish
thermal units
per
hour,
U is in
Btu/(ft
2
• h •
0
F),
A is
in
square
feet,
and
A7
is in
degrees Fahrenheit. Trans-
mission
coefficients
for
typical walls, windows,
and
roofs
as
well
as
methods
of
calculating
the
coefficient
for
the
combinations
of
materials
are
given
in
Chapter
25 of the
ASHRAE Handbook
of
Fundamentals
[12].
Cooling
Calculations
Heat gain throughout
the
structure, which makes
up the
external cooling load,
is
more
difficult
to
calculate than
heat
loss because
of the
effects
of
radiated heat
from
the
sun.
This additional heat source must
be
considered
in
addition
to the
heat gain
by
conduction
due to the
differ-
ence between outdoor
and
indoor temperatures. Sunlight
does
not
heat space
air
directly,
but it
raises
the
tempera-
ture
of
sunlit
surfaces
as a
result
of
absorbed radiation.
Many
factors
influence
the
amount
and
timing
of
solar heat reaching
the
space.
The
intensity
of
incident
solar radiation depends
on
latitude, time
of
year, time
of
day, cloud cover,
and
atmospheric pollution.
The
time
lag
between solar heat input
and
interior
air
tem-
perature rise
may
vary
from
a few
minutes
to
several
hours.
The lag is
affected
by the
surface color
of the
exterior,
the
heat storage capacity
and the
insulating
value
of the
construction,
and the
daily outdoor tem-
perature
range, among other
factors.
The
combined heat
from
both
the
higher outdoor
temperature
and
solar radiation moves progressively
through
walls
and
roof,
finally
raising
the
interior sur-
face
temperatures. Loss
from
those surfaces occurs
by
radiation
to
cooler
surfaces
and by
convection
to the
adjacent
air.
Air
warmed
by
convection expands,
becomes lighter, rises,
and is
replaced
by
cooler
air,
which
continues
the
convective process.
Except
for
minor reflected losses, sunlight passes
directly
through clear glass
and is
absorbed
by the
interior
surfaces
it
strikes. Their increased tempera-
ture
transfers heat
to
other
cooler
surfaces
by
reradia-
tion
and to the air by
convection.
Simply stated, solar heat gain
is
taken into account
by
using
a
higher outdoor temperature than actually would
exist
at the
time considered
for
each heat gain calcula-
tion.
The
ASHRAE
Handbook
of
Fundamentals
[12]
contains tables
of
cooling load temperature
differential
(CLTD)
data (for
use in
calculating conduction heat gain
through
sunlit walls
and
roofs)
and
cooling load
factors
(CLF) (for calculating
the
solar radiation through glass).
Both
sets
of
data include
the
effect
of
time delay
due to
thermal storage.
The
total resistance
to
heat
transfer
for
each type
of
construction
is
found
by
adding
the
resis-
tances
of its
components,
as
illustrated
in
Example
23-1.
Peak
Heat
Gain
The
peak heat gain
to a
space
is the
largest
sum of
external
and
internal
heat gains that occur simulta-
neously.
Heat removal capacity,
in the
form
of
ventila-
tion
or
cooling, equal
to the
peak heat gain must
be
available
to
maintain
the
design space temperature.
External heat gain results
from
an
outdoor tempera-
ture that
is
higher than
the
indoor temperature
as
well
as
from
solar radiation. Internal heat gain comes pri-
marily
from
operating motors
and
engines.
Air
Intake
and
Exhaust
Openings
Intakes
for
ventilation
air
should
be
through
screened
louvers that exclude rain, snow, birds,
and
insects.
Ducted intakes that
are
connected
to
air-handling units
with
filters
that exclude insects need only bird screens.
Nonducted intakes should include insect screens
or
filters.
All
screens
and filters
must
be
readily
accessi-
ble for
cleaning
or
replacement. Bird screens
do not
need mesh openings smaller than
25 mm
(
1
I
2
in.).
The
air
resistance
of filters
used
at
unducted wall intakes
should
not
exceed
24 Pa
(0.1
in. WC)
when clean
to
limit negative pressure
in the
space
(created
by
exhaust
fans)
to 63 Pa
(0.25
in.
WC);
low
negative
pressure makes doors easier
to
open
and
close.
Both
the
louver
and
screen should
be
constructed
of a
cor-
rosion-resistant material
or
should have
a
corrosion-
protective coating. Provide
an
intake damper
at
each
louver
in
cold climates, preferably with positive clo-
sure
on
failure
of its
pneumatic
or
electric actuator.
Hurricane-prone locations
may
warrant
an
additional
manually
operated damper
(on the
outdoor
air
intake)
that
can be
locked closed when
a
storm approaches.
Air
exhaust openings should
be
protected
from
the
weather
by a
wall louver, hood, penthouse,
or
weather