
.
Subsection 4.5 describes methods of shutting down the water flow under
overspeed conditions.
It describes ways to minimize the impact of small
overspeeds due to varying loads on a generator by the use of governors and
load controllers.
4.8.6 Cost of Generators
-
E
The costs of both synchronous and induction generators are related to
the size of the equipment.
The costs of both generators are based on
standard production models of the equipment. For this reason, the
"standard" synchronous generator is an BOO-rpm generator that is
manufactured for the gas- or diesel-fueled emergency or standby generator
market.
Figure 4.8-l is a graph showing the limits of cost versus kilowatt for
1800-rpm synchronous generators,
and Figure 4.8-2 is a graph of cost versus
kilowatt for induction generators.
These costs are in 1982 dollars.
4.8.7 Electrical Equipment Sizing
. The Category 1 developer will want to analyze all electrical loads to
determine which ones will be used at what times. You should tabulate the
electrical loads on the basis of use not only during the day but also at
night.
ihe standard household has many electrical appliances t!lat are used
during the day. However, these loads are not all used at the same time.
Table 3.1 in Subsection 3.1 gives standard loads used in a residence and
gives kWh of use per month for each p.iece of equipment.
?t
is evident from a
rtudy of this table that heating lcaji I've the
:.r
-iotter 1~92.
Careful study of the cable will indic.d:t' rxii.l?ds for
pro+ amraing a daily use pattern to keep the generators fully Io-ld:?d.
.
!I\e electrical loading required for the Category 1 deveiooer example
.
(.q!;" ..a- ',T ; ,:
8) has been deve!?ped to show how a power system yi'i 1 have to be
4.8-12