532 CHAPTER 13
change from 20% to 30% of maximum lift the flow at 30% would be about 50% more
than the flow at 20%. Likewise, if the lift increases from 40% to 50% the flow at 50%
would be about 50% more than at 40%.
With a linear valve having a constant pressure drop across it, equal incremental
changes in stem lift results in equal incremental changes in flow rate. For example,
if the lift increases from 40% to 50% of maximum, the flow rate changes from 40%
to 50% of maximum. Thus equal percentage is the more desirable characteristic for
most applications and is the one most widely used.
Pressure drop across control valves
In sizing or specifying the duty of the control valve the pressure drop across the
control valve must be determined for the design or maximum flow rate. In addition,
if it is known that a valve must operate at a flow rate considerably lower than the
maximum rate, the pressure drop at this lower flow rate must also be calculated. This
will be required to establish the range ability of the valve.
As a general rule of thumb the sum of following pressure drops at maximum flow
may be used for this purpose:
(a) 20% of the friction drop in the circuit
1
(excluding the valve).
(b) 10% of the static pressure of the vessel into which the circuit discharges up to
pressures of 200 psig, 20 psig from 200 to 400 psig, and 5% above 400 psig.
The static pressure is included to allow for possible changes in the pressure level in
the system (i.e., by changing the set point on the pressure controller on a vessel). The
percentage included for static pressure can be omitted in circuits such as recycle and
reflux circuits in which any change in pressure level in the receiver will be reflected
through the entire circuit. In some circuits the control valve will have to take a much
greater pressure drop than calculated from the percentages listed above. This occurs
in circuits where the control valve serves to bleed down fluid from a high-pressure
source to a low-pressure source. Examples are pressure control valves releasing gas
from a tower or streams going out to tankage from vessels operating at high pressure.
These are the circumstances where venturi or angle valves are used, as described
earlier.
Valve action on air failure
In the analysis of the design and operation of any process or utility system the question
always arises on the action of control valves in the system on instrument air failure.
1
A circuit generally includes all equipment between the discharge of a pump, compressor or vessel and
the next point downstream of which pressure is controlled. In most cases this latter point is a vessel.