For light flicker
ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
P
P
WKA
P
ST
S
KE
2
s
<
1
25
where S
WKA
is wind generator apparent power, P
WKA
is wind generator real power,
P
ST
is short-term flicker severity, S
KE
is short-circuit level at connection point, and
S
KSS
is short-circuit level at MV transformer station busbar.
The limit on the voltage change was based on the impedance of the circuit
between the point of connection and the MV transformer busbar together with the
apparent power of the wind-turbine generators. The voltage fluctuation limit was
simply based on the root of the sum of the squares of the short-circuit ratio of the
wind turbines while light flicker limit was the same calculation but with the value
of P
ST
measured for that type of wind turbine included. Simple rules such as these
are now of historical interest only but they do serve to illustrate the dominan t
influences on aspects of power qua lity.
Davidson (1995, 1996) carried out a comprehensive, two-year, measurement
campaign to investigate the effect of a wind farm in Wales on the power quality
of the 33 kV network to which it was connected. The 7.2 MW wind farm of
24 3 300 kW fixed-speed induction generator turbines was connected to a weak
33 kV overhead network with a short-circuit level of 78 MVA. Each wind turbine
was a WEG MS3-300 which are two-bladed, pitch-regulated machines with a
teetering hub. A pole amplitude modulated (PAM) induction machine was used to
give a rotor speed of 32 r.p.m. in low winds and 48 r.p.m. in high winds. An anti-
parallel thyristor soft-start unit was used to connect each generator to the network
and power factor correction capacitors were connected to each unit once the turbine
started generating. Each wind turbine fed the wind-farm electrical system via a local
0:66=11 kV transformer. Power was collected by two undergrou nd cable feeders
and passed to the 33 kV network via a conventional 11=33 kV distribution transfor-
mer with an on-load tap changer. The wind turbines were located along a ridge at
an elevation of 400 m in complex upland te rrain and so subject to turbulent winds.
Measurements to assess power quality were taken at the connection to the distribu-
tion network and at two wind turbines. The results are interesting as they indicate a
complex relationship of a general improvement in power quality due to the
connection of the generators, and hence the increase in short-circuit level, and a
slight increase in harmonic voltages caused by resonances of the generator wind-
ings with the power factor correction capacitors.
The operation of the wind farm raised the mean of the 33 kV voltage slightly but
reduced its standard deviation. This was expected as, in this case, the product of
injected active power and network resistance was approximately equal to the
product of the reactive power absorbe d and the inductive reactance of the 33 kV
connection. The effect of the generators was to increase the short-circuit level and so
reduce the variations in network voltage but with little effect on the steady-state
value. The connection of increasing numbers of induction generators caused a
dramatic reduction in negative phase sequence voltage from 1.5 percent with no
generators conn ected to less than 0.4 percent with all generators operating. This
584 ELECTRICAL SYSTEMS