
402 SECTION 6 Troubleshooting Using Control Schematics
permits the fan to operate in low speed when the
unit is in the heating cycle, and in high speed when
the unit is in the cooling cycle.
THE DOOR INTERLOCK SWITCH
The door interlock is shown on the schematic
as a normally open push button labeled (DIS). The
function of this switch is to permit the unit to oper-
ate only when the furnace door is closed. When
the door is opened, the 120-volt power supply is
broken to the unit. Most door interlock switches are
so designed that they are actually a two-position
switch. When the door is open, the switch can be
pulled out. This causes the switch to make connec-
tion so the unit can be serviced.
ELECTRONIC CONTROL
OF BLOWER MOTOR AND
COMPRESSOR LOCK-OUT
Many units employ electronic control for some
of their functions. Troubleshooting for electronic
circuit boards is generally accomplished by deter-
mining if the board has the proper input informa-
tion to obtain an output. If the inputs and outputs
are correct, the board is good and the problem lies
somewhere else in the circuit. The circuit board
shown in Figure 44–2 is designed to control the
blower for a cooling unit with gas or electric heat.
will cause terminal R to make connection with ter-
minals G and Y. When power is applied to terminal
Y, a circuit is completed to the condensing unit. The
other side of the condensing unit is connected to
terminal C, which completes the circuit back to the
control transformer. This starts the air conditioning
compressor and condenser fan.
Terminal G of the thermostat is connected to the
blower relay coil (BLR). When BLR coil energizes,
both BLR contacts change position. The normally
closed contact opens and prevents the possibility
that power can be applied to the low-speed terminal
of the blower fan motor. The normally open contact
closes and connects power to the high-speed termi-
nal of the motor. Notice that the indoor blower fan
operates in the high-speed position when the air
conditioning unit is started.
THE HEATING CYCLE
When the thermostat is in the heating position, a
decrease of temperature will cause the thermostat to
make connection between terminals R and W. This
permits a circuit to be completed through the automatic
gas valve (AGV). When the AGV is energized, gas is per-
mitted to ow to the main burner where it is ignited by
the pilot light. Two high-limit contacts are connected
in series with the automatic gas valve. One is labeled
auxiliary limit, and the other is labeled main
limit
. The wiring diagram shows the main limit to
be located in the fan-limit switch. The auxiliary limit
switch is in a separate location. Both of these switches
are normally closed and are shown to be temperature
activated. The schematic also shows that an increase
in temperature will cause them to open. Because both
are connected in series with the AGV, the circuit will be
broken to the valve if either one opens.
In the heating cycle, the indoor blower fan is con-
trolled by the fan switch. The fan switch is tempera-
ture activated. After the gas burner has been turned
on, the temperature of the furnace increases. When
the temperature has risen to a high enough level,
the fan switch will close and connect the low-speed
terminal of the blower motor to the power line.
Notice that the fan switch is connected in series with
the normally closed BLR contact. When BLR relay
is deenergized, the fan switch is permitted to control
the operation of the blower fan. The blower fan relay
Figure 44–2
Blower motor and compressor lock-out control board.
(Source: Delmar/Cengage Learning)