
210 SECTION 4 Transformers
designed in such a manner that it can be connected
to different primary voltages without changing the
value of the secondary voltage. In this example, it
is assumed that the secondary winding has a total
of 120 turns of wire. To maintain the proper turns
ratio, the primary would have 600 turns of wire
between C and 120; 1,040 turns between C and
208; and 1,200 turns between C and 240.
The transformer shown in Figure 19–19 contains
a single primary winding. The secondary winding,
however, has been tapped at several points. One of
the secondary lead wires is labeled C and is com-
mon to the other lead wires. When rated voltage
is applied to the primary, voltages of 12, 24, and
48 volts can be obtained at the secondary. It should
also be noted that this arrangement of taps permits
the transformer to be used as a center tapped trans-
former for two of the voltages. If a load is placed
across the lead wires labeled C and 24, the lead wire
labeled 12 becomes a center tap. If a load is placed
across the C and 48 lead wires, the 24-lead wire
becomes a center tap.
In this example, it is assumed the primary wind-
ing has 300 turns of wire. In order to produce the
proper turns ratio, it would require 30 turns of wire
between C and 12, 60 turns of wire between C and
24, and 120 turns of wire between C and 48.
The transformer shown in Figure 19–20 is similar
to the transformer in Figure 19–19. The transformer
in Figure 19–20, however, has multiple secondary
windings instead of a single secondary winding with
multiple taps. The advantage of the transformer in
Figure 19–20 is that the secondary windings are
electrically isolated from each other. These secondary
windings can be either step-up or step-down depend-
ing on the application of the transformer.
To check this answer, compute the volt amps of
both windings.
Primary
120 1.74 208.8
Secondary
500 0.417 208.8
The slight difference in answers is caused by round-
ing off the values.
Because the primary voltage is less than the
secondary voltage, the turns of wire in the primary
will be less also. The primary turns will be found by
dividing the turns of wire in the secondary by the
turns ratio.
N
P
N
S
__________
Turns Ratio
N
P
800
_____
4.17
N
P
192 turns
Figure 19–17 shows the transformer with all
completed values.
MULTIPLE TAPPED WINDINGS
It is not uncommon for transformers to be designed
with windings that have more than one set of lead
wires connected to the primary or secondary. The
transformer shown in Figure 19–18 contains a
secondary winding rated at 24 volts. The primary
winding contains several taps, however. One of the
primary lead wires is labeled C and is the common
for the other leads. The other leads are labeled 120,
208, and 240, respectively. This transformer is
E
S
500
I
S
0.417
N
S
800
E
P
120
I
P
1.74
N
P
192
Z = 1-200Ω
RATIO: 1:4.17
Figure 19–17
Transformer with completed
values. (Source: Delmar/Cengage Learning)