
736 Electric Power Distribution Handbook
High voltages can occur at heavy load (especially close to a voltage
regulator or capacitor bank on the distribution feeder).
• Relaying — Rely on the generator overvoltage relay to remove the
generator during high voltages. This may work out fine if the high
voltage conditions are infrequent.
• Impedance — A utility option would be to reduce the resistance of
the lines and transformers from the substation bus to the generator.
This would be done by using larger conductors on lines and cables
and specifying lower copper losses on transformers. Another option
is to build an express feeder to the generator.
• Regulation equipment — Another utility-side option is to add regula-
tion equipment (capacitors or regulators) to counteract the voltage
rise from the distributed generator.
Normally, the utility only needs to consider the service voltage, but utility
engineers may become involved with cases of high voltage within the facility.
ANSI C84.1 voltage standards account for voltage drop within a facility in
the utilization voltage standard — they do not account for a voltage rise that
generators cause.
Figure 14.15 shows a scenario where a generator just downstream of a
regulator can cause low voltage on the end of the circuit due to the regula-
tor’s line drop compensation controller. The power injected by the generator
fools the regulator into not raising voltage as much as it should.
Many regulators have a special concern — with reverse power, they ratchet
to the extreme tap, causing high or low voltage (EPRI TR-105589, 1995). Most
distribution regulators are bi-directional — they measure voltage on both
sides of the regulator, and power flow determines which side the regulator
uses for compensation. Bi-directional regulators are meant for distribution
system locations where the source may change directions, commonly nor-
mally-open loops that can be reconfigured. The regulator always tries to
regulate the voltage on the downstream side, determined by the direction
of power flow. If a downstream distributed generator injects enough real
power to reverse power flow on the regulator, the regulator thinks the source
has moved to the other side. It tries to regulate voltage on the upstream side
of the regulator (V
1
in Figure 14.16). If the measured voltage is higher than
the setpoint, the regulator changes its tap to try to lower the voltage. Nothing
happens to the voltage upstream of the generator (V
1
) since the utility source
holds the voltage constant. The regulator keeps trying to lower the voltage,
moving from tap to tap until the regulator ratchets all the way to the limit,
trying to lower voltage as much as possible.
What the regulator did was raise the voltage downstream of the regulator.
It raised the voltage when the feeder voltage was already high — to the
maximum amount. If the feeder voltage is lower than the regulator setpoint,
the opposite occurs: the regulator ratchets to the extreme tap setting that
1791_book.fm Page 736 Monday, August 4, 2003 3:20 PM
(C) 2004 by CRC Press LLC