
722 Electric Power Distribution Handbook
is a more severe neutral shift than is usual on a four-wire multigrounded
distribution circuit; it could represent an island being driven by distributed
generators. If a grounded-wye – grounded-wye transformer is used, the line-
to-ground voltages on the secondary are most sensitive. If a delta –
grounded-wye transformer is used, the line-to-line voltages on the secondary
are slightly more sensitive (although, overall the ability to sense primary
line-to-ground overvoltages is reduced by the delta – wye connection). A
grounded-wye – delta connection has line-to-ground voltages more sensitive
to the overvoltage (again, the ability to sense primary line-to-ground over-
voltages is reduced because of the transformer connection). The voltages
shown assume that the DG does not change the voltage on the primary or
secondary, when in reality the DG will normally be changing the voltage on
the secondary and maybe even the primary.
One important point is that all three voltages must be measured (whether
they are line-to-line or line-to-ground voltages). If voltages are assumed
balanced and only one of the three voltages is used, sustained overvoltages
could occur on the unmonitored phases.
Power quality disturbances also impact generators because the generator
must trip for voltage excursions. An analysis of EPRI’s Distribution Power
Quality (DPQ) data showed that the number of generator trips at most sites
is not particularly severe. Generators at most sites should have less than five
trips per year when using the UL 1741/IEEE 929 or IEEE P1547 settings (see
Figure 14.8). Trips become excessive only if the generator undervoltage relay-
ing is set at a very sensitive level.
Distributed generators based on inverters can do much of the interconnec-
tion relaying in the inverter controller. Utilities worry about inverter-based
relays, mainly because
• Inverter-based relays are not utility-grade.
•Testing in the field is very difficult. (They do not have external test
points for relay test sets.)
Inverter-based relays do have the advantage that they can perform anti-
islanding relaying as discussed in the previous section.
Many utilities require utility-grade relays for small installations, and essen-
tially all require them for large installations. But, what is a utility-grade relay?
There is no fixed definition, but normally, they must pass industry standards
(ANSI/IEEE C37.90-1989; ANSI/IEEE C37.90.1-1989; IEEE Std. C37.90.2-
1995). Utility-grade relays are normally more robust than industrial relays
and have test ports for external testing.
Inverter-based generators do not have external test ports for testing. Sep-
aration of the relaying component from the other controller functionalities
is difficult to do because the inverter controller uses the voltage and current
sensing for other control aspects.
1791_book.fm Page 722 Monday, August 4, 2003 3:20 PM
(C) 2004 by CRC Press LLC