This expression requires the humidity ratios v
1
and v
2
. Because no moisture is added
or removed in the heating section, it can be concluded from conservation of mass
that v
2
5 v
3
, so v
3
can be used in the above equation in place of v
2
.
Energy Balance
The mass flow rate of the refrigerant through the cooling coil m
r
can be related to
the mass flow rate of the dry air m
by means of an energy rate balance applied to the
dehumidifier section. With W
5 0, negligible heat transfer with the surroundings,
and no significant kinetic and potential energy changes, the energy rate balance
reduces at steady state to
0 5 m
#
r
h
i
2 h
e
1
m
#
a
h
a1
1 m
#
v1
h
v1
2 m
#
w
h
w
2
m
#
a
h
a2
1 m
#
v2
h
v2
where h
i
and h
e
denote the specific enthalpy values of the refrigerant entering and
exiting the dehumidifier section, respectively. Introducing m
v1
5 v
1
m
a
, m
v2
5 v
2
m
a
,
and m
#
w
5
v
1
2 v
2
m
#
a
0 5 m
#
r
h
i
2 h
e
1 m
#
a
h
a1
2 h
a2
1 v
1
h
g1
2 v
2
h
g2
2
v
1
2 v
2
h
f2
where the specific enthalpies of the water vapor at 1 and 2 are evaluated at the
saturated vapor values corresponding to T
1
and T
2
, respectively. Since the condensate
is assumed to exit as a saturated liquid at T
2
, h
w
5 h
f2
. Solving for the refrigerant
mass flow rate per unit mass of dry air flowing through the device
m
#
r
m
#
a
5
h
a1
2 h
a2
1 v
1
h
g1
2 v
2
h
g2
2
v
1
2 v
2
h
f2
h
e
2 h
i
The accompanying psychrometric chart, Fig. 12.11b, illustrates important features
of the processes involved. As indicated by the chart, the moist air first cools from
state 1, where the temperature is T
1
and the humidity ratio is v
1
, to state 2, where
the mixture is saturated (f
2
5 100%), the temperature is T
2
, T
1
, and the humidity
ratio is v
2
, v
1
. During the subsequent heating process, the humidity ratio remains
constant, v
2
5 v
3
, and the temperature increases to T
3
. Since all states visited are not
equilibrium states, these processes are indicated on the psychrometric chart by dashed
lines.
The example that follows provides an illustration involving dehumidification where
one of the objectives is the refrigerating capacity of the cooling coil.
Assessing Dehumidifier Performance
c c c c EXAMPLE 12.11 c
Moist air at 308C and 50% relative humidity enters a dehumidifier operating at steady state with a volumet-
ric flow rate of 280 m
3
/min. The moist air passes over a cooling coil and water vapor condenses. Condensate
exits the dehumidifier saturated at 108C. Saturated moist air exits in a separate stream at the same tem-
perature. There is no significant loss of energy by heat transfer to the surroundings and pressure remains
constant at 1.013 bar. Determine (a) the mass flow rate of the dry air, in kg/min, (b) the rate at which water
is condensed, in kg per kg of dry air flowing through the control volume, and (c) the required refrigerating
capacity, in tons.
SOLUTION
Known:
Moist air enters a dehumidifier at 308C and 50% relative humidity with a volumetric flow rate of 280 m
3
/min.
Condensate and moist air exit in separate streams at 108C.
Determine: Find the mass flow rate of the dry air, in kg/min, the rate at which water is condensed, in kg per kg
of dry air, and the required refrigerating capacity, in tons.
12.8 Analyzing Air-Conditioning Processes 747
c12IdealGasMixtureandPsychromet747 Page 747 6/29/10 11:57:46 AM user-s146 c12IdealGasMixtureandPsychromet747 Page 747 6/29/10 11:57:46 AM user-s146 /Users/user-s146/Desktop/Merry_X-Mas/New/Users/user-s146/Desktop/Merry_X-Mas/New