
VALVE REGULATED LEAD-ACID BATTERIES 24.43
24.8 APPLICATIONS OF VRLA BATTERIES TO UNINTERRUPTIBLE
POWER SUPPLIES
The major application of the VRLA battery is in the standby power market, ranging from
low-power (generally less than 5 KVA) applications such as emergency lighting or uninter-
ruptible power supplies (UPSs) for individual computers or work stations to high-power UPSs
in telecommunications facilities. A continuous supply of power is also critical in areas such
as banking, stock exchanges, hospitals, air traffic control centers etc., where brief interrup-
tions pose the risk of loss of critical data or hazards to health and safety. The low-power
UPS systems are generally used where a power loss is acceptable as long as there is sufficient
power to allow time for a safe shutdown of equipment. In a high-power application, the UPS
is typically required to provide power until a generator can be brought on line.
UPS systems are generally one of three basic designs: (1) standby or off-line; (2) on-line;
or (3) line interactive/hybrid. In most UPSs, AC power is fed to a battery charger/ rectifier
to provide the DC power to float charge the battery. The output of the battery is connected
to an inverter that converts the DC output of the battery and /or the battery charger/rectifier
to provide AC power needed to run the load. In the standby mode off-line UPS system, the
battery and inverter only come into play when the normal AC power fails. In the on-line
UPS system, the battery and inverter are always in the circuit. When the AC power fails,
the battery is already on-line supplying power to the inverter and no voltage dropout occurs,
as opposed to the off-line case where the voltage may drop out, typically for milliseconds
before the battery/inverter duo is switched into service. The on-line UPS system serves also
to smooth out any voltage fluctuations with the battery/inverter a continuously active element
in the circuit (see Sec. 23.9.6). The line interactive hybrid UPS system utilizes an automatic
voltage regulator and a special transformer to smooth any under- or over-voltages and to
ease the transition to complete battery backup only during outages of the input AC power.
A comprehensive treatment of UPS systems, markets and alternative UPS systems (e.g.,
flywheels) is given in Ref 18.
The experiences with VRLA batteries in the high-power UPS arena have served to dem-
onstrate the complex problems associated with these batteries compared to their flooded
counterparts. For most of the 20th century, lead-acid batteries for high-power UPS systems,
notably those employed in telecommunications facilities, were of the flooded type. Flooded
batteries have relatively large footprints, can spill acid and require periodic maintenance in
the form of watering, a costly operation for a UPS facility involving a large number of cells.
In the mid 1980s, with the advent of the VRLA battery and its maintenance-free feature,
there was immediate interest in replacing flooded with VRLA batteries. Initially, expectations
were that VRLA batteries would provide the roughly 20-year life found with flooded bat-
teries. Failures of VRLA batteries occurred after only a few years of service in many cases.
One unanticipated problem, negative plate self-discharge is considered below. In the year
2000, more realistic claims of 5–10 year battery life were the rule and there was a trend
back to flooded lead-acid for the high-power UPS applications. Some switching from lead-
acid to nickel-cadmium or nickel-metal hydride batteries for low-power UPS applications is
also taking place or being considered.
The life of a VRLA battery in a UPS application depends not only on the design of the
battery and the quality of its manufacture, but also very strongly on the usage. Most of the
performance figures quoted in the manufacturers’ specifications are for operating tempera-
tures of 25
⬚C. Any significant deviation from that temperature, higher or lower, can result
in poor performance, especially in the hands of a customer without knowledge of the proper
handling of VRLA batteries. For example, the optimal charging regime for a VRLA battery
is quite dependent on the temperature and must be modified for either higher or lower
temperatures (see Sec. 24.5.4). VRLA batteries that perform perfectly well in a constant
temperature environment may perform quite poorly, even exploding or catching fire, in an
outdoor cabinet in a telecommunications application in a variable climate.