IEC 61850 for Distributed Energy Resources 59-5
59.4.1 Client/Server Communication
e.most.important.ACSI.services.for.distributed.energy.resources.are.the.client-server.communication.
services..ey.include.services.such.as.the.following:
•
. GetDirectory:.When.a.client.wants.to.communicate.with.another.IED.it.can.retrieve.a.com-
plete
.list.of.the.names.of.all.accessible.objects.in.an.IED,.which.are.LDs,.LNs,.DOs,.and.data.
attributes.
•
. GetDataObjectDenition:.A.client.can.retrieve.the.data.types.for.all.objects.
•
. GetDataValues, SetDataValues:.e.values.of.the.objects.can.be.read.and.written.
•
. Reporting:.It.allows.an.event.driven.data.exchange.of.packed.values.between.a.server.and.a.client..
e.values.can.be.transmitted.by.an.IED.either.immediately.or.aer.some.buer.time.
•
. Logging:.e.server.provides.the.possibility.to.archive.data.for.later.retrieval.by.clients.
According
.to.the.actual.state.of.the.IEC.61850.standard,.the.client/server.communication.services.
have. to. be. mapped. to. the. Manufacturing. Message. Specication. (MMS)-protocol. that. is. based. on.
Ethernet.and.TCP/IP.(Figure.59.6)..e.MMS.standard.originally.was.developed.for.the.communica-
tion
.between.manufacturing.devices.like.numerically.controlled.machine.tools,.transport.systems.and.
supervisory.control.and.data.acquisition.(SCADA).systems..MMS.denes.a.structure.for.the.messages.
required.to.control.and.monitor.the.devices..It.is.not.concerned.with.the.way.the.messages.are.trans-
ferred
.between.devices.over.a.network..For.that.Ethernet.and.TCP/IP.is.used..e.data.objects.in.the.IEC.
61850.are.mapped.to.MMS.as.presented.in.Table.59.2.
e
.mapping.of.some.ACSI-services.to.MMS.is.already.shown.in.Figure.59.5..Figure.59.6.shows.a.
detailed.example.for.the.concrete.message.encoding.of.a.GetDirectory.ACSI-service.to.a.GetNameList.
message.of.the.MMS.protocol.
59.4.2 GOOSE
Another.ACSI.service.specied.by.the.IEC.61850-standard.is.the.so.called.Generic.Object.Oriented.
Substation.Event.(GOOSE)..It.is.a.mechanism.for.the.fast.transmission.of.events,.such.as.commands,.
alarms,.and.indications..A.single.GOOSE.broadcast-message.sent.by.an.IED.(publisher).can.be.received.
Ethernet link layer
IP
Ethernet physical layer with priority tagging
TCP
Sampled analog
values (SAV)
GOOSE
InformationReport
Read/Write
GetVarAcessAttributess
GetNameList
GetDirectory
GetDataObjectDefinition
GetDataValues/SetDataValues
ReportSettings
MMS
Client-server
comm.
Specific communication service mapping (SCSM)
Abstract communication services (ACSI)
Clock
synchronization
IP
UDP
SNTP
FIGURE 59.5 Comparison.between.ACSI.and.SCSM.