Foundation Fieldbus 35-7
35.9 Installation of Segments in Classied areas
Because.FF.requires.that.the.device.be.connected.to.a.network.to.perform.maintenance,.the.majority.
of.eldbus.installations.with.equipment.in.classied.areas.are.using.the.IS.technology..IS.technology.
allows.“live.working,”.meaning.all.eld.work.can.be.done.“hot,”.with.the.network.energized.and.com-
munications
.with.the.host.at.all.times..“Live.working”.means.you.can.work.without.continuous.gas.
testing.and.is.therefore.the.safest.way.to.protect.your.plant..An.alternative.to.IS,.or.its.equivalents.as.
described.below,.is.to.use.explosion-proof.technology.
One
.advantage.of.eldbus.technology.and.digital.communications,.however,.is.that.a.signicant.por-
tion
.of.the.work.that.in.the.past.had.to.be.done.at.the.device.for.analog.systems.(i.e.,.range.change).can.
now.be.completed.over.the.network.without.actually.having.to.go.to.the.physical.device.in.the.eld.
IS
.technology.is.based.in.the.reduction.of.the.energy.to.the.eld.to.levels.below.the.ignition.curves.
shown.in.Figure.35.4,.plus.a.safety.margin..For.analog.circuits,.this.is.typically.done.using.IS.barriers;.
however,.in.the.case.of.FF,.this.circuitry.is.either.incorporated.in.the.eldbus.power.conditioner.or.in.
the.eldbus.barrier.mounted.in.the.eld.junction.box.
A
.typical.FFPS.delivers.approximately.24–28.V.DC.and.currents.of.up.to.360.mA.power.to.the.eld.
segment..is.is.well.above.all.the.explosion.limit.curves.shown.on.Figure.35.4..FF.oers.two.additional.
technologies.other.than.an.IS.power.supply.that.is.limited.to.approximately.80–110.mA.at.around.12.V.
to.address.this.problem..One.solution.is.with.IS-equivalent.power.supplies.and.the.other.is.to.reduce.the.
available.energy.level.in.the.eld.using.the.above-mentioned.eldbus.barrier.technology.
35.9.1 FISCO—Fieldbus Intrinsically Safe COncept
Unlike.the.IS.entity.concept,.which.is.derived.from.theoretical.calculations,.the.FISCO.is.based.on.
actual.eld.trials.and.experiments.by.the.Physikalisch-Technische.Bundesaanstalt.(PTB).research.cen-
ter
.in.Germany..Because.this.IEC-60079-15.standard.is.based.on.experimentation,.all.installations.must.
operate.within.the.maximum.limits.within.which.the.experiments.were.conducted..ese.limits.are.that.
the.total.cable.length.of.the.system.is.limited.to.a.maximum.of.1000.m.in.IIC/Groups.A,.B.gases.and.
1900.m.in.IIB/Groups.C,.D.(limited.by.FF-831.and.therefore.identical.to.any.fieldbus.system)..The.
maximum.spur.length.for.any.FISCO.installation.is.60.m.per.spur.
Because
.the.FISCO.power.supply.must.operate.at.voltages.below.the.ignition.curve,.FISCO.systems.
are.not.able.to.connect.to.trunk.and.cable.combinations.that.are.as.long.as.non-IS.systems..Despite.this,.
FISCO.is.able.to.support.trunk.lengths.greater.than.500.m.with.full.system.current.loads..It.should.be.
500
Power supply characteristics
400
Short circuit current (mA)
300
200
100
12 14 16
Open circuit voltage (V)
IIB non-incendive
IIB intrinsically safe
IIC intrinsically safe
IIC non-incendive
18
FIGURE 35.4 Power.supply.characteristics.
© 2011 by Taylor and Francis Group, LLC