EN 13941:2009 (E)
Normally the most important restraints are:
a) the axial
restraint f-u, given by the pipe to soil friction, see B.3.2,
b) the horizontal restraint p-v, given by the horizontal modulus of soil reaction, see B.3.3.
B.3.2 Pipe to soil friction (axial)
The relevant ultimate values of the friction f
u
between PE casing and surrounding soil must be determined in due
consideration of the installation conditions such as:
a) type of backfill material and method and degree of soil compaction,
b) maximum and minimum groundwater levels,
c) presence of very stiff street covers preventing lateral soil displacements,
d) influence of possible future parallel excavations nearby the pipes,
e) “tunnel effect” due to possible increase in friction because of pipe diameter increase when heating up and
friction reduction because of pipe diameter decrease when cooling down.
For sandy soils the relative displacement
u
u
between pipe and surrounding soil required to reach the maximum
friction resistance
f
u
is approx. u
u
= 1 - 3 mm.
The maximum friction resistance can be calculated as:
f
u
=
µ
σ
n
where
σ
n
is the effective normal stress along the periphery of the PE casing.
For sandy soils the normal stress at a casing can be calculated on basis of a state of soil pressure at rest, giving
the friction per unit length of pipe:
⋅⋅−+⋅⋅⋅
+
=
2
0
22
1
c
scv
D
GD
K
F
πγπσµ
where:
K
o
is the coefficient of soil pressure at rest, K
o
= 1 - sin
ϕ
;
For sandy soils K
o
may normally be valued at 0,5;
G is the effective selfweight of pipe with water;
v
σ
is the effective soil stress at pipe centre level.
For granular soils:
()
wswwsv
HZH −+⋅=
γγσ
for H
w
< Z
v
σ
=
γ
s
• Z for H
w
≥ Z
where
H
w